Indicative fire tests to investigate heat insulation scenario of wired glasses sprayed with intumescent coatings

被引:19
作者
Chuang, Ying-Ji [1 ]
Tang, Chieh-Hsin [2 ]
Chen, Po-Hung [3 ]
Chuang, Ying-Hung [1 ]
Lin, Ching-Yuan [1 ]
机构
[1] Natl Taiwan Univ Sci & Technol, Dept Architecture, Taipei 10607, Taiwan
[2] Tungnan Univ, Dept Construct Technol, Taipei 222, Taiwan
[3] Kao Yuan Univ, Dept Architecture, Kaohsiung 821, Taiwan
关键词
Glass; Intumescent coating; Radiation; Fire test; INDUCED THERMAL FIELDS; WINDOW GLASS; IGNITION; BEHAVIOR;
D O I
10.1007/s11998-009-9218-9
中图分类号
O69 [应用化学];
学科分类号
081704 ;
摘要
This study used three fire exposure samples with areas of 1 m x 1 m to conduct standard furnace fire tests. Through radiometer and theoretical analysis, the heat insulation of wired glass sprayed with intumescent coatings was measured. Test results indicate that after using an intumescent coating with a thickness of 0.3 mm, wired glass surface will generate a heat insulation layer that will dramatically reduce radiant energy levels due to thermal expansion. Results from this study suggest the use for a grid shape of intumescent coating because of the ease of application to wired glass and the fact that wired glass with an intumescent coating has proven to be the most feasible heat insulation material that can be practically applied in designated fireproof compartments of buildings.
引用
收藏
页码:143 / 150
页数:8
相关论文
共 32 条
  • [1] [Anonymous], 2004, 14815 CNS
  • [2] [Anonymous], 2005, 12514 CNS
  • [3] [Anonymous], 2003, 8158 EN
  • [4] [Anonymous], 1997, 263 UL
  • [5] [Anonymous], 1987, 47622 BS
  • [6] [Anonymous], 1997, 10B UL
  • [7] [Anonymous], 1995, 109 GA
  • [8] [Anonymous], 2000, 16341 BS EN
  • [9] [Anonymous], 1997, E119 ASTM
  • [10] [Anonymous], 2006, 3008 ISO