Experimental investigation of adverse effect of frost formation on microchannel evaporators, part 1: Effect of fin geometry and environmental effects

被引:47
作者
Moallem, Ehsan [1 ]
Hong, Tommy [1 ]
Cremaschi, Lorenzo [1 ]
Fisher, Daniel E. [1 ]
机构
[1] Oklahoma State Univ, Sch Mech & Aerosp Engn, Stillwater, OK 74078 USA
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2013年 / 36卷 / 06期
关键词
Frost; Microchannel; Surface temperature; Fin geometry; Heat pump; Capacity reduction; TUBE HEAT-EXCHANGERS; PERFORMANCE; SYSTEMS; SURFACE; GROWTH;
D O I
10.1016/j.ijrefrig.2012.09.009
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study experimentally investigated the frost growth on louvered folded fins in microchannel heat exchangers when used in outdoor air-source heat pump systems. The effects of surface temperature, fin geometries, and air environmental conditions were studied. The overall aim was to isolate and quantify the effect of geometry from surface temperature effects. Experimental data of frost weight, local frost thickness, air pressure drop across the coils, time of frost defrost cycles and heat transfer rates were recorded. Data showed that the frosting-time and the frost growth rates depended mainly on the local fin surface temperature. Lower fin density was beneficial because it delayed the blockage of the air flow. The fin length and fin depth had minor effects on frosting performance. The air humidity had a fairly significant effect on rate of frost formation while air velocity seemed to have a small effect on the frost growth rate. Published by Elsevier Ltd.
引用
收藏
页码:1762 / 1775
页数:14
相关论文
共 19 条
[1]  
[Anonymous], THESIS TH DELFT
[2]  
[Anonymous], 2008, 210240 AHRI
[3]   Innovations in energy efficient and environmentally friendly space-conditioning systems [J].
Garimella, S .
ENERGY, 2003, 28 (15) :1593-1614
[4]  
Hong T, 2012, ASHRAE TRAN, V118, P1101
[5]  
Kim J.-H., 2003, 1195 ASHRAE
[6]   Performance evaluation of a window room air conditioner with microchannel condensers [J].
Kim, MH ;
Bullard, CW .
JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME, 2002, 124 (01) :47-55
[7]   EFFECT OF FROST GROWTH ON THE PERFORMANCE OF LOUVERED FINNED TUBE HEAT-EXCHANGERS [J].
KONDEPUDI, SN ;
ONEAL, DL .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1989, 12 (03) :151-158
[8]   A one-dimensional model for frost formation on a cold flat surface [J].
Lee, KS ;
Kim, WS ;
Lee, TH .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1997, 40 (18) :4359-4365
[9]  
Moallem E., 2012, 1589RP ASHRAE
[10]  
Moallem E., 2010, P ASME ATI UIT C THE