Monitoring of power transformers using the transfer function method

被引:120
作者
Leibfried, T [1 ]
Feser, K
机构
[1] Siemens AG, Transformatorenwerk, Nurnberg, Germany
[2] Univ Stuttgart, Inst Power Transmiss & High Voltage Technol, D-7000 Stuttgart, Germany
关键词
D O I
10.1109/61.796226
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The transfer function concept is well known as an additional method of evaluating the impulse test of power transformers in the test laboratory. Another application for this method is monitoring of power transformers in sen ice. According to the method of how to measure transient signals for the calculation of transfer functions, two kinds of monitoring can be distinguished: Off-line and On-line monitoring. Both kinds of monitoring as well as their influencing factors are discussed with on-site measurements on power transformers in service.
引用
收藏
页码:1333 / 1341
页数:9
相关论文
共 5 条
  • [1] BOSS P, 1991, CIGRE SC 12 C GRAZ J
  • [2] *IEC, 1978, 599 IEC
  • [3] MALEWSKI R, 1988, IEEE T POWER DELIVER, V3
  • [4] MALEWSKI R, 1992, CIGRE, V1
  • [5] NORTON ET, 1986, IEEE PES 1986 TRANSM