The detection of the closing moments of a vacuum circuit breaker by vibration analysis

被引:34
作者
Meng, YP [1 ]
Jia, SL [1 ]
Shi, ZQ [1 ]
Rong, MZ [1 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
关键词
closing moments; short-time energy (STE); signal-to-noise ratio (SNR); vacuum circuit beakers (VCBs); vibration signal;
D O I
10.1109/TPWRD.2005.855475
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The vibration signals during the closing operation of three-phase vacuum circuit breakers (VCBs) were recorded for detecting the closing moment of each pole. The short-time energy (STE) analysis of the vibration signals with a moving Hamming window is used to derive the closing moments both under no-load conditions and load conditions. By determining a proper length for the moving window, the improved signal-to-noise ratio by the STE analysis greatly facilitates the identification of the closing moments. Under no-load condition, the results obtained from the vibration signals are in good agreement with those measured by the contact timing signals. Under load conditions, it is found that the effect of the making current on the detection results is too tenuous to be neglected. This makes it possible to apply this method to online detection of the closing moments of VCBs.
引用
收藏
页码:652 / 658
页数:7
相关论文
共 16 条
[1]  
[Anonymous], SCH PSYCHOL Q
[2]  
deGrijp MHB, 1996, AFRICON '96 - 1996 IEEE AFRICON : 4TH AFRICON CONFERENCE IN AFRICA, VOLS I & II, P880, DOI 10.1109/AFRCON.1996.563009
[3]   NONINVASIVE CONDITION ASSESSMENT AND EVENT TIMING FOR POWER CIRCUIT-BREAKERS [J].
HESS, DP ;
PARK, SY ;
TANGRI, MK ;
VOUGIOUKAS, SG ;
SOOM, A ;
DEMJANENKO, V ;
ACHARYA, RS ;
BENENSON, DM ;
WRIGHT, SE .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (01) :353-360
[4]  
HUA L, 1999, J TEST MEAS TECHNOL, V13, P21
[5]   CIGRE WG 13.06 studies on the reliability of single pressure SF6-gas high-voltage circuit-breakers [J].
Janssen, ALJ ;
Brunke, JH ;
Heising, CR ;
Lanz, W .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (01) :274-282
[6]  
JUN Y, 1999, J NANJING U POSTS TE, V19, P79
[7]  
Kezunovic A, 2002, 2002 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, VOLS 1-3, CONFERENCE PROCEEDINGS, P559, DOI 10.1109/PESS.2002.1043299
[8]   MECHANICAL FAILURE-DETECTION OF CIRCUIT-BREAKERS [J].
LAI, ML ;
PARK, SY ;
LIN, CC ;
NAIDU, H ;
SOOM, A ;
REINHORN, AM ;
LEE, YH ;
SOONG, TT ;
DEMJANENKO, V ;
BENENSON, DM ;
WRIGHT, SE .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :1724-1731
[9]  
LI S, 1997, T CHINA ELECTROTECHN, V12, P42
[10]  
MAZZA G, 1981, ELECTRA, V79, P21