Exposure control system performance was evaluated during aircraft paint spraying at a military facility. Computational fluid dynamics (CFD) modeling, tracer gas testing, and exposure monitoring examined contaminant exposure vs. crossflow ventilation velocity. CFD modeling using the RNG k-epsilon turbulence model showed exposures to simulated methyl isobutyl ketone of 294 and 83.6 ppm, as a spatial average of five worker locations, for velocities of 0.508 and 0.381 m/s (100 and 75 fpm), respectively. In tracer gas experiments, observed supply/exhaust velocities of 0.706/0.503m/s (136/99 fpm) were termed full-flow, and reduced velocities were termed 3/4-flow and half-flow. Half-flow showed higher tracer gas concentrations than 3/4-flow, which had the lowest time-averaged concentration, with difference in log means significant at the 95% confidence level. Half-flow compared to full-flow and 3/4-flow compared to full-flow showed no statistically significant difference. CFD modeling using these ventilation conditions agreed closely with the tracer results for the full-flow and 3/4-flow comparison, yet not for the 3/4-flow and half-flow comparison. Full-flow conditions at the painting facility produced a velocity of 0.528 m/s (104 fpm) midway between supply and exhaust locations, with the supply rate of 94.4 m(3)/s (200,000 cfm) exceeding the exhaust rate of 68.7 m(3)/s (146,000 cfm). Ventilation modifications to correct this imbalance created a midhangar velocity of 0.406 m/s (80.0 fpm). Personal exposure monitoring for two worker groups-sprayers and sprayer helpers ("hosemen")-compared process duration means for the two velocities. Hexavalent chromium (Cr[VI]) exposures were 500 vs. 360 mu g/m(3) for sprayers and 120 vs. 170 mu g/m(3) for hosemen, for 0.528 m/s (104 fpm) and 0.406 m/s (80.0 fpm), respectively. Hexamethylene diisocyanate (HDI) monomer means were 32.2 vs. 13.3 mu g/m(3) for sprayers and 3.99 vs. 8.42 mu g/m(3) for hosemen. Crossflow velocities affected exposures inconsistently, and local work zone velocities were much lower. Aircraft painting contaminant control is accomplished better with the unidirectional crossflow ventilation presented here than with other observed configurations. Exposure limit exceedances for this ideal condition reinforce continued use of personal protective equipment.
引用
收藏
页码:167 / 181
页数:15
相关论文
共 15 条
[1]  
American Conference of Governmental Industrial Hygienists (ACGIH), 2010, IND VENT MAN REC PRA, p[13, 135]
[2]  
[Anonymous], COMPUTATIONAL FLUID, DOI DOI 10.1007/978-94-007-4488-2_1
[3]  
[Anonymous], 2003, NIOSH MANUAL ANAL ME
[4]  
Ashley K., NIOSH manual of analytical methods, V4th
[5]   Polyisocyanates in occupational environments: A critical review of exposure limits and metrics [J].
Bello, D ;
Woskie, SR ;
Streicher, RP ;
Liu, YC ;
Stowe, MH ;
Eisen, EA ;
Ellenbecker, MJ ;
Sparer, J ;
Youngs, F ;
Cullen, MR ;
Redlich, CA .
AMERICAN JOURNAL OF INDUSTRIAL MEDICINE, 2004, 46 (05) :480-491
[6]   Hexavalent chromium and isocyanate exposures during military aircraft painting under crossflow ventilation [J].
Bennett, James S. ;
Marlow, David A. ;
Nourian, Fariba ;
Breay, James ;
Hammond, Duane .
JOURNAL OF OCCUPATIONAL AND ENVIRONMENTAL HYGIENE, 2016, 13 (05) :356-371
[7]  
Lin CH, 2005, ASHRAE TRAN, V111, P764
[8]  
Patankar S.V., 1980, Numerical Heat Transfer and Fluid Flow, P30
[9]  
U. S. Department of Defense, 2010, 421102NF UFC US DEP, P12
[10]  
U. S. Department of Health and Human Services, 2006, DHHS NIOSH PUBL