Investigation of Separated Two-Phase Thermosiphon Loop for Relieving the Air-Conditioning Loading in Datacenter

被引:19
作者
Daraghmeh, Hafiz M. [1 ]
Sulaiman, Mohammed W. [1 ]
Yang, Kai-Shing [2 ]
Wang, Chi-Chuan [1 ]
机构
[1] Natl Chiao Tung Univ, Dept Mech Engn, Hsinchu 300, Taiwan
[2] Ind Technol Res Inst, Green Energy & Environm Res Labs, Hsinchu 300, Taiwan
关键词
datacenter; free cooling; two-phase flow; thermosiphon; separated loop; PFA pipe; MECHANICAL REFRIGERATION; INTEGRATED-SYSTEM; SIMULATION; PERFORMANCE; RATIO; MODE;
D O I
10.3390/en12010105
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This study investigates the feasibility of using R-134a filled separated two-phase thermosiphon loop (STPTL) as a free cooling technique in datacenters. Two data center racks one of them is attached with fin and tube thermosiphon were cooled by CRAC unit (computer room air conditioning unit) individually. Thermosiphon can help to partially eliminate the compressor loading of the CRAC; thus, energy saving potential of thermosiphon loop was investigated. The condenser is a water-cooled design and perfluoroalkoxy pipes were used as adiabatic riser/downcomer for easier installation and mobile capability. Tests were conducted with filling ratio ranging from 0 to 90%. The test results indicate that the energy saving increases with the rise of filling ratio and an optimum energy savings of 38.7% can be achieved at filling ratios of 70%, a further increase of filling ratio leads to a reduction in energy saving. At a low filling ratio like 10%, the evaporator starves for refrigerant and a very uneven air temperature distribution occurring at the exit of data rack. The uneven temperature distribution is relieved considerably when the evaporator is fully flooded. It is also found that the energy saving is in line with the rise of system pressure. Overfilling of the evaporator may lead to a decline of system pressure. A lower thermal resistance occurs at high filling ratios and higher ambient temperature.
引用
收藏
页数:18
相关论文
共 23 条
[1]   Experimental investigations and modeling of a loop thermosyphon for cooling with zero electrical consumption [J].
Chehade, Ali ;
Louahlia-Gualous, Hasna ;
Le Masson, Stephane ;
Lepinasse, Eric .
APPLIED THERMAL ENGINEERING, 2015, 87 :559-573
[2]   A review of current status of free cooling in datacenters [J].
Daraghmeh, Hafiz M. ;
Wang, Chi-Chuan .
APPLIED THERMAL ENGINEERING, 2017, 114 :1224-1239
[3]   Experiment research on influence factors of the separated heat pipe system, especially the filling ratio and Freon types [J].
Ding, Tao ;
Cao, Han Wen ;
He, Zhi Guang ;
Li, Zhen .
APPLIED THERMAL ENGINEERING, 2017, 118 :357-364
[4]   Numerical modelling of the temperature distribution in a two-phase closed thermosyphon [J].
Fadhl, Bandar ;
Wrobel, Luiz C. ;
Jouhara, Hussam .
APPLIED THERMAL ENGINEERING, 2013, 60 (1-2) :122-131
[5]   Development of an integrated air conditioner with thermosyphon and the application in mobile phone base station [J].
Han, Linjun ;
Shi, Wenxing ;
Wang, Baolong ;
Zhang, Penglei ;
Li, Xianting .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (01) :58-69
[6]  
Imura H., 1979, NASA ADS, V45, P712
[7]   Three-dimensional CFD simulation of geyser boiling in a two-phase closed thermosyphon [J].
Jouhara, Hussam ;
Fadhl, Bandar ;
Wrobel, Luiz C. .
INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2016, 41 (37) :16463-16476
[8]   Experimental investigation of small diameter two-phase closed thermosyphons charged with water, FC-84, FC-77 and FC-3283 [J].
Jouhara, Hussam ;
Robinson, Anthony J. .
APPLIED THERMAL ENGINEERING, 2010, 30 (2-3) :201-211
[9]   Experimental investigation of effective parameters and correlation of geyser boiling in a two-phase closed thermosyphon [J].
Khazaee, I. ;
Hosseini, R. ;
Noie, S. H. .
APPLIED THERMAL ENGINEERING, 2010, 30 (05) :406-412
[10]   EXPERIMENTAL INVESTIGATION OF GEYSER BOILING IN AN ANNULAR 2-PHASE CLOSED THERMOSIPHON [J].
LIN, TF ;
LIN, WT ;
TSAY, YL ;
WU, JC ;
SHYU, RJ .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1995, 38 (02) :295-307