Experimental performance analysis of a packaged R290 refrigeration unit retrofitted with R170 for ultra-low temperature freezing

被引:28
作者
Carlos Rodriguez-Criado, Juan [1 ]
Antonio Exposito-Carrillo, Jose [1 ,2 ]
Peris Perez, Bernardo [2 ]
Dominguez-Munoz, Fernando [2 ]
机构
[1] Intarcon SL, Bulevar Ios Santos 34, Lucena 14900, Spain
[2] Univ Malaga, Dept Ingn Mecan, Escuela Ingn Ind, C Doctor Ortiz Ramos s n, Malaga 29071, Spain
关键词
Hydrocarbons; Ethane; Propane; Retrofit; Ultra-low temperature; EJECTOR; SYSTEM; CYCLE; ENERGY;
D O I
10.1016/j.ijrefrig.2021.11.015
中图分类号
O414.1 [热力学];
学科分类号
摘要
While the global refrigeration capacity installed in ultra-low temperature applications is considerably lower than in standard refrigeration, the interest in such systems has risen during the last months due to their emerging demand for the preservation of mRNA vaccines. Several theoretical studies can be found in the literature for ultra-low temperature applications. However, there is still a lack of reliable experimental data that may be used for the models validation and, thereby, to perform more rigorous investigations. In light of this, the present manuscript proposes an ultra-low temperature refrigeration unit based on an indirect cascade system, developed by retrofitting a standard low-temperature R290 packaged unit. In this investigation, firstly, the suitability of the original components is assessed and, then, the unit is experimentally tested within a wide range of operating conditions. Thereby, the system's reliability is evaluated by assessing different parameters, such as discharge, condensing and evaporating temperatures and performance ratios. The main results showed a successful behaviour at the operating conditions tested, exhibiting a COP that ranged from 0.6 to 1.6 for cold room temperatures between -80 degrees C and -65 degrees C, respectively.
引用
收藏
页码:105 / 114
页数:10
相关论文
共 29 条
[11]   Theoretical study on a modified single-stage autocascade refrigeration cycle with auxiliary phase separator [J].
Liu, Jiarui ;
Liu, Ye ;
Yan, Gang ;
Yu, Jianlin .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 122 :181-191
[12]   Performance analysis of an advanced ejector-expansion autocascade refrigeration cycle [J].
Liu, Ye ;
Yu, Jianlin .
ENERGY, 2018, 165 :859-867
[13]   Ultralow-temperature refrigeration systems: Configurations and refrigerants to reduce the environmental impact [J].
Mota-Babiloni, Adrian ;
Joybari, Mahmood Mastani ;
Navarro-Esbri, Joaquin ;
Mateu-Royo, Carlos ;
Barragan-Cervera, Angel ;
Amat-Albuixech, Marta ;
Moles, Francisco .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 111 :147-158
[14]   Evaluation of the potential recovery of compressor heat losses to enhance the efficiency of refrigeration systems by means of thermoelectric generation [J].
Navarro-Peris, Emilio ;
Corberan, Jose Miguel ;
Ancik, Zdenek .
APPLIED THERMAL ENGINEERING, 2015, 89 :755-762
[15]   Thermodynamic performance evaluation of a cascade refrigeration system with mixed refrigerants: R744/R1270, R744/R717 and R744/RE170 [J].
Parolin Massuchetto, Luiz Henrique ;
Correa do Nascimento, Raiza Barcelos ;
Rocha de Carvalho, Stella Maia ;
de Araujo, Hugo Valenca ;
Hallak d'Angelo, Jose Vicente .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 106 :201-212
[16]   Energy and exergy performance evaluation of a three-stage auto-cascade refrigeration system using low-GWP alternative refrigerants [J].
Qin, Yanbin ;
Li, Nanxi ;
Zhang, Hua ;
Liu, Baolin .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 126 :66-75
[17]   Energetic and exergetic performance comparison of cascade refrigeration system using R170-R161 and R41-R404A as refrigerant pairs [J].
Roy, Ranendra ;
Mandal, Bijan Kumar .
HEAT AND MASS TRANSFER, 2019, 55 (03) :723-731
[18]   Performance comparison of natural refrigerants based cascade systems for ultra-low-temperature applications [J].
Sarkar, Jahar ;
Bhattacharyya, Souvik ;
Lal, Arjun .
INTERNATIONAL JOURNAL OF SUSTAINABLE ENERGY, 2013, 32 (05) :406-420
[19]  
Schulz M., 2014, Regulation (EU) No 517/2014 of the European Parliament and of the Council of 16 on fluorinated greenhouse gases and repealing Regulation (EC) No 842/2006, DOI [10.4271/1999-01-0874, DOI 10.4271/1999-01-0874]
[20]   Principal effective factors on the dynamic pull-down performance of a zeotropic mixture based ultra-low temperature freezer [J].
Song, Yulong ;
Wang, Haidan ;
Cao, Feng .
APPLIED THERMAL ENGINEERING, 2021, 183