Prevention of reliability degradation from recloser-fuse miscoordination due to distributed generation

被引:138
作者
Chaitusaney, Surachai [1 ]
Yokoyama, Akihiko [1 ]
机构
[1] Univ Tokyo, Dept Elect Engn, Tokyo 1138656, Japan
关键词
distributed generation (DG); distribution system; fuse; generation threshold; protection miscoordination; recloser; reliability;
D O I
10.1109/TPWRD.2007.915899
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Distributed generation (DG) may bring about reliability degradation, instead of reliability enhancement, due to recloser-fuse miscoordination. For the prevention of this reliability degradation, this paper proposes a method to find the threshold value of the DG capacity, beyond which recloser-fuse coordination is lost. Mathematical equations for protective devices are used to set up the protection settings and calculate the threshold value. Three reliability indices-SAIFI, SAIDI, and ENS-are evaluated and compared with the study cases in the reliability test system RBTS bus 2. The results show that the proposed method is effective to prevent the deterioration of system reliability. In addition, a simple modification to the protection system is presented as a preliminary solution.
引用
收藏
页码:2545 / 2554
页数:10
相关论文
共 17 条
  • [1] A RELIABILITY TEST SYSTEM FOR EDUCATIONAL PURPOSES - BASIC DISTRIBUTION-SYSTEM DATA AND RESULTS
    ALLAN, RN
    BILLINTON, R
    SJARIEF, I
    GOEL, L
    SO, KS
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (02) : 813 - 820
  • [2] [Anonymous], P IEEE
  • [3] [Anonymous], 2003, IEEE Std. 1547-2003, P1
  • [4] [Anonymous], P IEEE RUR EL POW C
  • [5] [Anonymous], 1997, C371121996 IEEE
  • [6] Barker PP, 2000, 2000 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-4, P1645, DOI 10.1109/PESS.2000.868775
  • [7] Determination of allowable penetration levels of distributed generation resources based on harmonic limit considerations
    Bhowmik, A
    Maitra, A
    Halpin, SM
    Schatz, JE
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (02) : 619 - 624
  • [8] Billinton R., 1984, Reliability Evaluation of Power Systems, DOI DOI 10.1007/978-1-4615-7731-7
  • [9] Blackburn J. L., 1998, PROTECTIVE RELAYING
  • [10] Chaitusaney S, 2006, 2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6, P2673