A Noniterative Optimized Algorithm for Shunt Active Power Filter Under Distorted and Unbalanced Supply Voltages

被引:57
作者
Kanjiya, Parag [1 ]
Khadkikar, Vinod [1 ]
Zeineldin, Hatem H. [1 ,2 ]
机构
[1] Masdar Inst Sci & Technol, Abu Dhabi, U Arab Emirates
[2] Cairo Univ, Giza, Egypt
关键词
Active power filter (APF); harmonic compensation; optimized control; power quality; unity power factor (UPF); STRATEGY; COMPENSATION; HARMONICS; DESIGN; SYSTEM; LOADS;
D O I
10.1109/TIE.2012.2235394
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In this paper, a single-step noniterative optimized algorithm for a three-phase four-wire shunt active power filter under distorted and unbalanced supply conditions is proposed. The main objective of the proposed algorithm is to optimally determine the conductance factors to maximize the supply-side power factor subject to predefined source current total harmonic distortion (THD) limits and average power balance constraint. Unlike previous methods, the proposed algorithm is simple and fast as it does not incorporate complex iterative optimization techniques (such as Newton-Raphson and sequential quadratic programming), hence making it more effective under dynamic load conditions. Moreover, separate limits on odd and even THDs have been considered. A mathematical expression for determining the optimal conductance factors is derived using the Lagrangian formulation. The effectiveness of the proposed single-step non-iterative optimized algorithm is evaluated through comparison with an iterative optimization-based control algorithm and then validated using a real-time hardware-in-the-loop experimental system. The real-time experimental results demonstrate that the proposed method is capable of providing load compensation under steady-state and dynamic load conditions, thus making it more effective for practical applications.
引用
收藏
页码:5376 / 5390
页数:15
相关论文
共 26 条
[1]  
Akagi H, 2007, INSTANTANEOUS POWER
[2]   Active Power Filter Control Strategy With Implicit Closed-Loop Current Control and Resonant Controller [J].
Angulo, Mauricio ;
Ruiz-Caballero, Domingo A. ;
Lago, Jackson ;
Heldwein, Marcelo Lobo ;
Mussa, Samir Ahmad .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (07) :2721-2730
[3]  
[Anonymous], 1992, IEEE Std. 519
[4]  
[Anonymous], 2013, Power generation, operation, and control
[5]  
[Anonymous], IEEE Std. 1459-2010
[6]   A Shunt Active Power Filter With Enhanced Performance Using ANN-Based Predictive and Adaptive Controllers [J].
Bhattacharya, Avik ;
Chakraborty, Chandan .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (02) :421-428
[7]   An improved control algorithm of shunt active filter for voltage regulation, harmonic elimination, power-factor correction, and balancing of nonlinear loads [J].
Chandra, A ;
Singh, B ;
Singh, BN ;
Al-Haddad, K .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2000, 15 (03) :495-507
[8]   Meeting IEEE-519 current harmonics and power factor constraints with a three-phase three wire active power filter under distorted source voltages [J].
Chang, Gary W. ;
Yeh, Chia-Ming ;
Chen, Wi-Cheng .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1648-1654
[9]   A new approach for optimal shunt active power filter control considering alternative performance indices [J].
Chang, GW .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (01) :406-413
[10]   Optimisation-based strategy for shunt active power filter control under non-ideal supply voltages [J].
Chang, GW ;
Yeh, CM .
IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS, 2005, 152 (02) :182-190