On tracking the source location of voltage sags and utility shunt capacitor switching transients

被引:35
作者
Chang, Gary W. [1 ]
Chao, Ju-Peng [1 ]
Huang, Hunter M. [1 ]
Chen, Cheng-I [1 ]
Chu, Shou-Yung [1 ]
机构
[1] Natl Chung Cheng Univ, Dept Elect Engn, Chiayi 621, Taiwan
关键词
fault current; power quality (PQ); shunt capacitor switching transients; voltage sag;
D O I
10.1109/TPWRD.2008.923143
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a new procedure to track the disturbance source location of voltage sags and shunt capacitor switching transients in a power system based on branch current measurements. In the proposed method, the power-quality metering locations are first determined by the sensitivity of the system fault-current level to the fault voltage. Then, a current deviation index for representing the change of each measured branch current rms magnitudes before and after the disturbance is calculated to track the disturbance source location within an area confined by the directions of the top-priority branches. The IEEE 30-bus benchmark system and an actual transmission system with recorded power-quality disturbance events are use to illustrate the usefulness of the proposed method. Simulation results obtained by the proposed method are also compared with those obtained by a previously developed approach and by actual recorded data. By observing the results, it shows that the proposed method is efficient and accurate to track the source area of voltage sags or shunt capacitor switching transients.
引用
收藏
页码:2124 / 2131
页数:8
相关论文
共 13 条
[1]  
Bollen M.H.J., 2000, Series on Power Engineering
[2]   An efficient approach for tracking transients generated by utility shunt capacitor switching [J].
Chang, GW ;
Shih, MH ;
Chu, SY ;
Thallam, R .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (01) :510-512
[3]   Fault location using voltage measurements [J].
Galijasevic, Z ;
Abur, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (02) :441-445
[4]  
Grainger J. J., 1994, Power System Analysis, V1st
[5]   A time-domain procedure for locating switched capacitors in power distribution systems [J].
Kim, J ;
Grady, WM ;
Arapostathis, A ;
Soward, JC ;
Bhatt, SC .
IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (04) :1044-1049
[6]   Method for voltage-sag-source detection by investigating slope of the system trajectory [J].
Li, C ;
Tayjasanant, T ;
Xu, W ;
Liu, X .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2003, 150 (03) :367-372
[7]   An optimal monitoring program for obtaining voltage sag system indexes [J].
Olguin, G ;
Vuinovich, F ;
Bollen, MHJ .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (01) :378-384
[8]   A direction finder for power quality disturbances based upon disturbance power and energy [J].
Parsons, AC ;
Grady, WM ;
Powers, EJ ;
Soward, JC .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (03) :1081-1086
[9]   Applying distance relay for voltage sag source detection [J].
Pradhan, AK ;
Routray, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :529-531
[10]   Characterization of distribution power quality events with Fourier and wavelet transforms [J].
Santoso, S ;
Grady, WM ;
Powers, EJ ;
Lamoree, J ;
Bhatt, SC .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (01) :247-254