The airborne transmission of infection between flats in high-rise residential buildings: Particle simulation

被引:81
作者
Gao, N. P. [1 ]
Niu, J. L. [1 ]
Perino, M. [2 ]
Heiselberg, P. [3 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China
[2] Politecn Torino, DENER, I-10129 Turin, Italy
[3] Aalborg Univ, Hybrid Ventilat Ctr, DK-9000 Aalborg, Denmark
关键词
Particles; Lagrangian method; Eulerian method; Transport; Deposition; LARGE-EDDY SIMULATION; NUMERICAL-SIMULATION; INDOOR ENVIRONMENTS; AEROSOL DEPOSITION; INFLUENZA-A; AIR-FLOW; DISPERSION; TRANSPORT; DROPLETS;
D O I
10.1016/j.buildenv.2008.03.016
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Several case clusters occurred in high-rise residential buildings in Hong Kong in the 2003 SARS (the severe acute respiratory syndrome) epidemic, which motivated a series of engineering investigations into the possible airborne transport routes. It is suspected that, driven by buoyancy force, the polluted air that exits the window of the lower floor may re-enter the immediate upper floor through the window on the same side. This cascade effect has been quantified and reported in a previous paper, and it is found that, by tracer gas concentration analysis, the room in the adjacent upstairs may contain up to 7% of the air directly from the downstairs room. In this study, after validation against the experimental data from literatures, Eulerian and Lagrangian approaches are both adopted to numerically investigate the dispersion of expiratory aerosols between two vertically adjacent flats. It is found that the particle concentration in the upper floor is two to three orders of magnitude lower than in the source floor. 1.0 mu m particles disperse like gaseous pollutants. For coarse particles larger than 20.0 mu m, strong deposition on solid surfaces and gravitational settling effect greatly limit their upward transport. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:402 / 410
页数:9
相关论文
共 37 条
[21]   Modelling and measurement of airflow and aerosol particle distribution in a ventilated two-zone chamber [J].
Lu, WZ ;
Howarth, AT ;
Adam, N ;
Riffat, SB .
BUILDING AND ENVIRONMENT, 1996, 31 (05) :417-423
[22]   Improved numerical simulation of aerosol deposition in an idealized mouth-throat [J].
Matida, EA ;
Finlay, WH ;
Lange, CF ;
Grgic, B .
JOURNAL OF AEROSOL SCIENCE, 2004, 35 (01) :1-19
[23]   Droplet fate in indoor environments, or can we prevent the spread of infection? [J].
Morawska, L. .
INDOOR AIR, 2006, 16 (05) :335-347
[24]  
MURAKAMI S, 1992, ASHRAE TRAN, V98, P82
[25]   Toward understanding the risk of secondary airborne infection: Emission of respirable pathogens [J].
Nicas, M ;
Nazaroff, WW ;
Hubbard, A .
JOURNAL OF OCCUPATIONAL AND ENVIRONMENTAL HYGIENE, 2005, 2 (03) :143-154
[26]   On-site quantification of re-entry ratio of ventilation exhausts in multi-family residential buildings and implications [J].
Niu, J. ;
Tung, T. C. W. .
INDOOR AIR, 2008, 18 (01) :12-26
[27]   Review of aerosol transmission of influenza A virus [J].
Tellier, Raymond .
EMERGING INFECTIOUS DISEASES, 2006, 12 (11) :1657-1662
[28]   Particle deposition in turbulent duct flows - comparisons of different model predictions [J].
Tian, Lin ;
Ahmadi, Goodarz .
JOURNAL OF AEROSOL SCIENCE, 2007, 38 (04) :377-397
[29]   Particle dispersion and deposition in direct numerical and large eddy simulations of vertical pipe flows [J].
Uijttewaal, WSJ ;
Oliemans, RVA .
PHYSICS OF FLUIDS, 1996, 8 (10) :2590-2604
[30]   Large eddy simulation of particle deposition in a vertical turbulent channel flow [J].
Wang, Q ;
Squires, KD .
INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 1996, 22 (04) :667-683