Pathogen cross-transmission via building sanitary plumbing systems in a full scale pilot test-rig

被引:55
作者
Gormley, Michael [1 ]
Aspray, Thomas J. [1 ]
Kelly, David A. [1 ]
Rodriguez-Gil, Cristina [1 ]
机构
[1] Heriot Watt Univ, Sch Energy Geosci Infrastruct & Soc, Riccarton Campus, Edinburgh, Midlothian, Scotland
关键词
HONG-KONG; CONTAMINATION; BIOFILM; TOILET; IMPACT; SARS;
D O I
10.1371/journal.pone.0171556
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
The WHO Consensus Document on the epidemiology of the SARS epidemic in 2003, included a report on a concentrated outbreak in one Hong Kong housing block which was considered a 'super-spreading event'. The WHO report conjectured that the sanitary plumbing system was one transmission route for the virus. Empty U-traps allowed the aerosolised virus to enter households from the sewerage system. No biological evidence was presented. This research reports evidence that pathogens can be aerosolised and transported on airstreams within sanitary plumbing systems and enter buildings via empty U-traps. A sanitary plumbing system was built, representing two floors of a building, with simulated toilet flushes on the lower floor and a sterile chamber with extractor fan on the floor above. Cultures of a model organism, Pseudomonas putida at 10(6) - 10(9) cfu ml(-1) in 0.85% NaCl were flushed into the system in volumes of 6 to 20 litres to represent single or multiple toilet flushes. Air and surface samples were cultured on agar plates and assessed qualitatively and semi-quantitatively. Flushing from a toilet into a sanitary plumbing system generated enough turbulence to aerosolise pathogens. Typical sanitary plumbing system airflows (between 20-30 ls(-1)) were sufficient to carry aerosolised pathogens between different floors of a building. Empty U-traps allowed aerosolised pathogens to enter the chamber, encouraging cross-transmission. All parts of the system were found to be contaminated post-flush. Empty U-traps have been observed in many buildings and a risk assessment indicates the potential for high risk cross-transmission under defect conditions in buildings with high pathogen loading such as hospitals. Under defective conditions (which are not uncommon) aerosolised pathogens can be carried on the airflows within sanitary plumbing systems. Our findings show that greater consideration should be given to this mode of pathogen transmission.
引用
收藏
页数:13
相关论文
共 29 条
[1]  
[Anonymous], 1882015 ANSI ASHRAE
[2]   A soil-based microbial biofilm exposed to 2,4-D: bacterial community development and establishment of conjugative plasmid pJP4 [J].
Aspray, TJ ;
Hansen, SK ;
Burns, RG .
FEMS MICROBIOLOGY ECOLOGY, 2005, 54 (02) :317-327
[3]   Survival of Salmonella in bathrooms and toilets in domestic homes following salmonellosis [J].
Barker, J ;
Bloomfield, SF .
JOURNAL OF APPLIED MICROBIOLOGY, 2000, 89 (01) :137-144
[4]   The potential spread of infection caused by aerosol contamination of surfaces after flushing a domestic toilet [J].
Barker, J ;
Jones, MV .
JOURNAL OF APPLIED MICROBIOLOGY, 2005, 99 (02) :339-347
[5]  
British Standards Institute, 2003, 1469812003 BS EN ISO
[6]  
British Standards Institution, 2000, 120562 BS EN
[7]   EVALUATION OF COUNTING ERROR DUE TO COLONY MASKING IN BIOAEROSOL SAMPLING [J].
CHANG, CW ;
HWANG, YH ;
GRINSHPUN, SA ;
MACHER, JM ;
WILLEKE, K .
APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 1994, 60 (10) :3732-3738
[8]  
CIBSE, 2013, TM13 MIN RISK LEG DI
[9]  
Gebra CP, 1975, APPL ENVIRON MICROB, V30, P229