Performance of Shunt Active Power Filter Under Sensor Failure

被引:0
作者
Sharma, Shivangni [1 ]
Verma, Vimlesh [1 ]
机构
[1] Natl Inst Technol Patna, Dept Elect Engn, Patna, Bihar, India
来源
2017 IEEE INTERNATIONAL WIE CONFERENCE ON ELECTRICAL AND COMPUTER ENGINEERING (IEEE WIECON-ECE 2017) | 2017年
关键词
Harmonics; Active Power Filter; Sensor; Fault;
D O I
暂无
中图分类号
TP301 [理论、方法];
学科分类号
081202 ;
摘要
This paper shows the performance of Shunt Active Power Filter (SAPF) under failure of various sensors. The SAPF have been developed on the basis of Instantaneous Reactive Power Theory (also known as P-Q theory) to generate reference current for harmonic mitigation. The controller aims at the power quality improvement of a power system with the non-linear load by using SAPF (Shunt Active Power Filter). In general, P-Q theory based controller requires the information of three load currents and three source voltages. Hence, the controller requires information from six sensors. Therefore, failure of any one sensor will affect the overall performance of the SAPF. Here, performance of SAPF under failure of single and multiple sensors is studied. A comparative study has been performed to demonstrate effect on the performance of SAPF under various sensor failure conditions. The power system with compensation has been analyzed in MATLAB/SIMULINK environment through simulations for the conditions of sensor failures, which serves as functional candidates for the P-Q algorithm. Different combinations (i.e., failure of sensors) have been studied to observe its effect on THD in source current. Further, an algorithm for successful compensation of one voltage and one current sensor failure (simultaneously or individually) have been proposed under balanced conditions and successfully verified on MATLAB/SIMULINK platform.
引用
收藏
页码:165 / 168
页数:4
相关论文
共 11 条
[1]   INSTANTANEOUS REACTIVE POWER COMPENSATORS COMPRISING SWITCHING DEVICES WITHOUT ENERGY-STORAGE COMPONENTS [J].
AKAGI, H ;
KANAZAWA, Y ;
NABAE, A .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1984, 20 (03) :625-630
[2]  
Bai HF, 2017, IEEE ENER CONV, P3004, DOI 10.1109/ECCE.2017.8096551
[3]   An instantaneous reactive volt-ampere compensator and harmonic suppressor system [J].
Chatterjee, K ;
Fernandes, BG ;
Dubey, GK .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 1999, 14 (02) :381-392
[4]  
Freitas CM, 2014, IEEE IND ELEC, P5163, DOI 10.1109/IECON.2014.7049286
[5]  
Gyugyi L., 1976, Active ac power filters, P529
[6]  
IEEE, 5192014 IEEE
[7]  
Nedeljkovic D, 2009, ELEKTROTEH VESTN, V76, P275
[8]   The design and implementation of a shunt active power filter based on source current measurement [J].
Ozdemir, Engin ;
Ucar, Mehmet ;
Kesler, Metin ;
Kale, Murat .
IEEE IEMDC 2007: PROCEEDINGS OF THE INTERNATIONAL ELECTRIC MACHINES AND DRIVES CONFERENCE, VOLS 1 AND 2, 2007, :608-+
[9]  
Singh B, 2015, POWER QUALITY PROBLEMS AND MITIGATION TECHNIQUES, pXI
[10]   Adaptive Frequency Domain Control of PWM Switched Power Line Conditioner [J].
Williams, Stephen M. ;
Hoft, Richard G. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 1991, 6 (04) :665-670