Experimentally Validated Computational Fluid Dynamics Model for Data Center With Active Tiles

被引:24
作者
Athavale, Jayati [1 ]
Joshi, Yogendra [1 ]
Yoda, Minami [1 ]
机构
[1] Georgia Inst Technol, George W Woodruff Sch Mech Engn, Atlanta, GA 30332 USA
关键词
active tiles; CFD modeling; failure analysis; local cooling; data center;
D O I
10.1115/1.4039025
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an experimentally validated room-level computational fluid dynamics (CFD) model for raised-floor data center configurations employing active tiles. Active tiles are perforated floor tiles with integrated fans, which increase the local volume flow rate by redistributing the cold air supplied by the computer room air conditioning (CRAC) unit to the under-floor plenum. The numerical model of the data center room consists of one cold aisle with 12 racks arranged on both sides and three CRAC units sited around the periphery of the room. The commercial CFD software package FUTURE FACILITIES 6SIGMADCX is used to develop the model for three configurations: (a) an aisle populated with ten (i.e., all) passive tiles; (b) a single active tile and nine passive tiles in the cold aisle; and (c) an aisle populated with all active tiles. The predictions from the CFD model are found to be in good agreement with the experimental data, with an average discrepancy between the measured and computed values for total flow rate and rack inlet temperature less than 4% and 1.7 degrees C, respectively. The validated models were then used to simulate steady-state and transient scenarios following cooling failure. This physics-based and experimentally validated room-level model can be used for temperature and flow distributions prediction and identifying optimal number and locations of active tiles for hot spot mitigation in data centers.
引用
收藏
页数:10
相关论文
共 18 条
[1]  
Abdelmaksoud W.A., 2010, 2010 12th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, P1
[2]   Innovative Approaches of Experimentally Guided CFD Modeling for Data Centers [J].
Alissa, H. A. ;
Nemati, K. ;
Sammakia, B. ;
Ghose, K. ;
Seymour, M. ;
Schmidt, R. .
2015 31ST ANNUAL SEMICONDUCTOR THERMAL MEASUREMENT, MODELING & MANAGEMENT SYMPOSIUM (SEMI-THERM), 2015, :176-184
[3]  
Alissa H.A., 2015, INT ELECT PACKAGING
[4]  
Arghode V. K., 2013, 2 INT WORKSH HEAT TR, P246
[5]  
Arghode VK, 2015, P IEEE SEMICOND THER, P163, DOI 10.1109/SEMI-THERM.2015.7100155
[6]  
Athavale J, 2016, INTERSOC C THERMAL T, P1162, DOI 10.1109/ITHERM.2016.7517680
[7]  
Bash CE, 2006, 2006 PROCEEDINGS 10TH INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONICS SYSTEMS, VOLS 1 AND 2, P445
[8]  
Beitelmal M. H., 2009, INTERPACK200989035 A
[9]   Viability of dynamic cooling control in a data center environment [J].
Boucher, Timothy D. ;
Auslander, David M. ;
Bash, Cullen E. ;
Federspiel, Clifford C. ;
Patel, Chandrakant D. .
JOURNAL OF ELECTRONIC PACKAGING, 2006, 128 (02) :137-144
[10]  
Future Facilities, 2016, 6SIGMAROOM