A numerical investigation on the mixing factor and particle deposition velocity for enclosed spaces under natural ventilation

被引:14
作者
Liu, Xiaoran [1 ]
Li, Fei [1 ]
Cai, Hao [1 ]
Zhou, Bin [1 ]
Shi, Shanshan [2 ]
Liu, Jinxiang [1 ]
机构
[1] Nanjing Tech Univ, Dept HVAC, Coll Urban Construct, Nanjing 210009, Jiangsu, Peoples R China
[2] Nanjing Univ, Sch Architecture & Urban Planning, Nanjing 210007, Jiangsu, Peoples R China
基金
中国国家自然科学基金;
关键词
y mixing factor; particle deposition velocity; computational fluid dynamics (CFD); multi-zone model; AIR-FLOW; CONTAMINANT DISPERSION; INDOOR ENVIRONMENTS; MULTIZONE; CFD; BUILDINGS; TRANSPORT; ROOMS; RATES; TIME;
D O I
10.1007/s12273-018-0497-x
中图分类号
O414.1 [热力学];
学科分类号
摘要
The multi-zone model is widely used to predict airflow and contaminant transport in large buildings under natural or mechanical ventilation. Selecting appropriate mixing factors and particle deposition velocities for the multi-zone model can compensate for the errors resulting from the model's well-mixing assumption. However, different room types, air change rates and ventilation modes can result in different mixing factors and particle deposition velocities. This study selected three typical room types: Z-type, L-type, and rectangle type (R-type). For each room type, the mixing factors and particle deposition velocities were investigated by the CFD model under different natural ventilation rates (0.5 h(-1), 1 h(-1), 3 h(-1), 6 h(-1), 12 h(-1) and 20 h(-1)) and modes (door-inlet, window-inlet). The results showed that the mixing factor of the Z-type room was the highest, and the mixing factors of these rooms were 1.32, 1.28 and 1.13, respectively. In addition, the mixing factors presented a V-shaped distribution as a function of the air exchange rate under the window-inlet mode. The particle deposition velocity increased as the air change rate increased, and also demonstrated that the V-shaped curves as a function of particle size (0.05 m, 0.1 m, 0.5 m, 1 m, 2.5 m, 5 m) varied under different air change rates and room types. The results of mixing factors and particle deposition velocities for different room types, air change rates and ventilation modes can be used to improve the accuracy of the multi-zone model.
引用
收藏
页码:465 / 473
页数:9
相关论文
共 39 条
[1]  
[Anonymous], 2004, VENT ACC IND AIR QUA
[2]  
[Anonymous], 2011, ANSYS FLUENT 14 0 US
[3]   Multizone airflow Modeling in buildings: History and theory [J].
Axley, James .
HVAC&R RESEARCH, 2007, 13 (06) :907-928
[4]  
Bartak M., 2001, 7th Int. Build. Perform. Simul. Assoc. Conf, P773
[5]  
BRIEF RS, 1960, AIR ENG, V2, P39
[6]   Study on the impacts of human walking on indoor particles dispersion using momentum theory method [J].
Cao, Shi-Jie ;
Cen, Dongdong ;
Zhang, Weirong ;
Feng, Zhuangbo .
BUILDING AND ENVIRONMENT, 2017, 126 :195-206
[7]   Review of relationship between indoor and outdoor particles: I/O ratio, infiltration factor and penetration factor [J].
Chen, Chun ;
Zhao, Bin .
ATMOSPHERIC ENVIRONMENT, 2011, 45 (02) :275-288
[8]   Ventilation performance prediction for buildings: A method overview and recent applications [J].
Chen, Qingyan .
BUILDING AND ENVIRONMENT, 2009, 44 (04) :848-858
[9]  
CONSTANCE JD, 1970, POWER, V114, P56
[10]   Influence of air change rates on indoor CO2 stratification in terms of Richardson number and vorticity [J].
Deng, Hua-Yan ;
Feng, Zhuangbo ;
Cao, Shi-Jie .
BUILDING AND ENVIRONMENT, 2018, 129 :74-84