High current interruption performance of vacuum interrupter with double-TMF contacts

被引:0
作者
Lamara, T. [1 ]
Gentsch, D. [2 ]
Hencken, K. [1 ]
机构
[1] ABB Switzerland Ltd, Corp Res, Baden, Switzerland
[2] ABB Calor Emag Mittelspannung GmbH, Ratingen, Germany
来源
25TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV 2012) | 2012年
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A new two-contact system with double-TMF structure is investigated regarding its potential for high current interruption. It consists in two co-axial TMF contacts in which the inner contact has a disk-shape structure (spiral contacts) and an outer contact with cup-shape structure. This contacts assembly gives some advantages over the single-TMF contacts one, as the high current constricted arc might split between both, inner and outer contacts or commute to the outer contact and continues its rotation. For both scenarios we normally get a larger distribution of the arc energy over the contacts surface. B-field simulation and Lorentz forces evaluation were carried out to understand the interaction between two assumed co-existing arc columns. Single phase current interruption tests were carried out to compare the performance of double-TMF contacts system with the single-TMF one. The double-TMF vacuum interrupter has revealed superior current interruption performance, 25% higher than the single-TMF one.
引用
收藏
页码:251 / 254
页数:4
相关论文
共 8 条
[1]  
[Anonymous], 55 IEEE HOLM C EL CO
[2]  
Dullni E., 1989, IEEE T PLASMA SCI, V17
[3]   High-speed observations of arc modes and material erosion on RMF- and AMF-contact electrodes [J].
Gentsch, D ;
Shang, W .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2005, 33 (05) :1605-1610
[4]  
Pavelescu D., 2006, 22 INT S DISCH EL IN
[5]  
Schellekens H., 2008, ISDEIV2008 23 INT S
[6]   Current zero behavior of vacuum interrupters with bipolar and quadrupolar AMF contacts [J].
Steinke, K ;
Lindmayer, M .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2003, 31 (05) :934-938
[7]   A test method for 50 Hz capability of vacuum interrupter materials [J].
Wilkening, ED ;
Lindmayer, M ;
Reininghaus, U .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1997, 4 (06) :854-856
[8]   Transition from constricted to diffuse vacuum arc modes during high AC current interruption [J].
Zalucki, Z ;
Janiszewski, J .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 1999, 27 (04) :991-1000