Envelope retrofit and air-conditioning operational strategies for reduced energy consumption in mosques in hot climates

被引:39
作者
Budaiwi, Ismail M. [1 ]
Abdou, Adel A. [1 ]
Al-Homoud, Mohammad S. [1 ]
机构
[1] King Fahd Univ Petr & Minerals, Architectural Engn Dept, Dhahran 31261, Eastern Prov, Saudi Arabia
关键词
intermittent operation; energy savings; thermal comfort; mosques; hot-humid climate; COOLING-TECHNOLOGIES; SIMULATION; BUILDINGS;
D O I
10.1007/s12273-012-0092-5
中图分类号
O414.1 [热力学];
学科分类号
摘要
Thermal performance of buildings is mainly determined by their thermo-physical and operational characteristics as well as the prevailing climatic conditions. Mosques which represent a unique type of building in terms of construction and operation can be major consumers of cooling energy, particularly in hot climates, if not properly designed and operated. In this study, energy modeling and simulation is utilized to identify potential energy savings due to envelope retrofitting measures and air-conditioning (A/C) operational strategies while maintaining acceptable thermal conditions. Results revealed a good potential for energy reductions when proper thermal retrofitting and operational strategies are employed. As much as 26% reduction in annual cooling energy is obtained when applying roof and wall insulation and reducing air infiltration to 0.5 ACH. By implementing a proper A/C operational strategy and employing system efficiency improvements, the required cooling energy can be reduced by around 36%. The total reduction in cooling energy consumption due to combined A/C system and envelope retrofit measures can be as much as 48%. A number of recommendations pertaining to mosque design, retrofitting and A/C operational strategies are derived. These are expected to be of great use to mosque designers and operators worldwide, but particularly in hot climates.
引用
收藏
页码:33 / 50
页数:18
相关论文
共 23 条
[1]  
Abdou A, 2005, J ENG SCI ABDULAZIZ, V16, P165
[2]   A case study for influence of building thermal insulation on cooling load and air-conditioning system in the hot and humid regions [J].
Aktacir, Mehmet Azmi ;
Buyukalaca, Orhan ;
Yilmaz, Tuncay .
APPLIED ENERGY, 2010, 87 (02) :599-607
[3]   Thermal comfort in air-conditioned mosques in the dry desert climate [J].
Al-ajmi, Farraj F. .
BUILDING AND ENVIRONMENT, 2010, 45 (11) :2407-2413
[4]  
Al-homoud M.S., 2005, J KING SAUD U ENG SC, V16, P185, DOI [10.4197/Eng.16-1.11, DOI 10.4197/ENG.16-1.11]
[5]   Assessment of monitored energy use and thermal comfort conditions in mosques in hot-humid climates [J].
Al-Homoud, Mohammad S. ;
Abdou, Adel A. ;
Budaiwi, Ismail M. .
ENERGY AND BUILDINGS, 2009, 41 (06) :607-614
[6]  
[Anonymous], 2003, ASHRAE APPL HDB
[7]  
Arabian Gulf Cooperation Council AGCC, 1984, REG THERM INS BUILD, P30
[8]  
ASHRAE, 2009, ASHRAE FUND HDB SI C, P43
[9]  
Bou-Saada TE, 1995, P 30 INT EN CONV ENG
[10]  
CARROLL WL, 1993, ASHRAE TRAN, V99, P928