Steam jet ejector cooling powered by waste or solar heat

被引:58
作者
Meyer, A. J. [1 ]
Harms, T. M. [1 ]
Dobson, R. T. [1 ]
机构
[1] Univ Stellenbosch, Dept Mech & Mechatron Engn, ZA-7602 Matieland, South Africa
基金
新加坡国家研究基金会;
关键词
Steam jet ejector; Solar energy; Solar refrigeration; Waste heat; SYSTEM; REFRIGERATOR; SIMULATION; CYCLE;
D O I
10.1016/j.renene.2008.03.020
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
A small scale steam jet ejector experimental setup was designed and manufactured. This ejector setup consists of an open loop configuration and the boiler operate in the temperature range of T-b=85-140 degrees C. The typical evaporator liquid temperatures range from T-e=5 degrees C to 10 degrees C while the typical water-cooled condenser pressure ranges from P-c=1.70 kPa to 5.63 kPa (T-c=15-35 degrees C). The boiler is powered by two 4 kW electric elements while a 3 kW electric element simulates the cooling load in the evaporator. The electric elements are controlled by means of variacs. Primary nozzles with throat diameters of 2.5 mm, 3.0 mm and 3.5 mm are tested while the secondary ejector throat diameter remains unchanged at 18 mm. These primary nozzles allow the boiler to operate in the temperature range of T-b=85-110 degrees C. When the nozzle throat diameter is increased, the minimum boiler temperature decreases. A primary nozzle with a 3.5 mm throat diameter was tested at a boiler temperature of T-b=95 degrees C, an evaporator temperature of T-e=10 degrees C and a critical condenser pressure of P-crit=2.67 kPa (22.6 degrees C). The system's COP is 0.253. In a case study the experimental data of a solar powered steam jet ejector air conditioner is investigated. Solar powered steam ejector air conditioning systems are technical and economical viable when compared to conventional vapour compression air conditioners. Such a system can either utilise flat plate or evacuated tube solar thermal collectors depending on the type of solar energy available. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:297 / 306
页数:10
相关论文
共 27 条
[1]   An experimental study of an ejector cycle refrigeration machine operating on R113 [J].
Al-Khalidy, N .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (08) :617-625
[2]   A solar ejector cooling system using refrigerant R134a in the Athens area [J].
Alexis, GK ;
Karayiannis, EK .
RENEWABLE ENERGY, 2005, 30 (09) :1457-1469
[3]   A small capacity steam-ejector refrigerator: experimental investigation of a system using ejector with movable primary nozzle [J].
Aphornratana, S ;
Eames, IW .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1997, 20 (05) :352-358
[4]   Simulation and optimization of a LiBr solar absorption cooling system with evacuated tube collectors [J].
Assilzadeh, F ;
Kalogirou, SA ;
Ali, Y ;
Sopian, K .
RENEWABLE ENERGY, 2005, 30 (08) :1143-1159
[5]  
CENGAL YA, 2002, THERMODYNAMICS ENG A, pCH16
[6]   Ejectors: applications in refrigeration technology [J].
Chunnanond, K ;
Aphornratana, S .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2004, 8 (02) :129-155
[7]   An experimental investigation of a steam ejector refrigerator: the analysis of the pressure profile along the ejector [J].
Chunnanond, K ;
Aphornratana, S .
APPLIED THERMAL ENGINEERING, 2004, 24 (2-3) :311-322
[8]   A THEORETICAL AND EXPERIMENTAL-STUDY OF A SMALL-SCALE STEAM JET REFRIGERATOR [J].
EAMES, IW ;
APHORNRATANA, S ;
HAIDER, H .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1995, 18 (06) :378-386
[9]   THE JET-PUMP CYCLE - A LOW-COST REFRIGERATOR OPTION POWERED BY WASTE HEAT [J].
EAMES, IW ;
APHORNRATANA, S ;
SUN, DW .
HEAT RECOVERY SYSTEMS & CHP, 1995, 15 (08) :711-721
[10]   An experimental investigation of steam ejectors for applications in jet-pump refrigerators powered by low-grade heat [J].
Eames, IW ;
Wu, S ;
Worall, M ;
Aphornratana, S .
PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART A-JOURNAL OF POWER AND ENERGY, 1999, 213 (A5) :351-361