Numerical simulation of thermal performance for super large-scale wet cooling tower equipped with an axial fan

被引:50
作者
Dang, Zhigang [1 ]
Zhang, Zhengqing [1 ]
Gao, Ming [1 ]
He, Suoying [1 ]
机构
[1] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Shandong, Peoples R China
基金
中国国家自然科学基金;
关键词
Super large-scale natural draft wet cooling towers; Numerical simulation; Thermal performance; Axial fan; Water dropping potential energy; WATER; FLOW; MEDIA;
D O I
10.1016/j.ijheatmasstransfer.2019.01.111
中图分类号
O414.1 [热力学];
学科分类号
摘要
For the super large-scale natural draft wet cooling towers (S-NDWCTs), the higher rain zone produces water dropping potential energy which can be used to drive an axial fan, meanwhile, the larger diameter deteriorate the whole ventilation performance. Based on these issues, a three dimensional (3D) numerical model for a S-NDWCT equipped with an axial fan was established to analyze the thermal performance at different fan diameters and fan power. In order to evaluate the influence of fan, one dimensionless number m, represents the ratio between the fan diameter and the cooling tower diameter, was introduced in this paper, as well as air velocity uniformity coefficient psi(vel) and air temperature uniformity coefficient psi(tem). Simulation results manifested that, compared with natural draft pattern, the thermal performance and ventilation performance of S-NDWCT with an axial fan improve partly according to these two uniformity coefficient and several thermal performance parameters, and they improve continuously with the increasing of fan diameter and fan power. At the given fan rotate speed (20 rpm), the water temperature drop Delta T, ventilation rate G, Merkel number N and cooling efficiency eta enhance persistently as the diameter of the fan increases, while these parameters enhance firstly, and then reduce at the given power (300 kW). Under 15.0 m fan diameter (m = 0.125) and 300 kW fan power conditions, compared with natural draft pattern, Delta T, G, N, and eta all reach to the maximum of 931 degrees C, 31,549 kg/s, 1.65 and 53.5%, and enhance by 0.14 degrees C, 611 kg/s, 0.04 and 0.8%, respectively. It demonstrates that the cooling tower shows out the outstanding thermal and ventilation performance when the diameter ratio m is 0.125. (C) 2019 Elsevier Ltd. All rights reserved.
引用
收藏
页码:220 / 234
页数:15
相关论文
共 41 条
[1]   CFD simulation of wet cooling towers [J].
Al-Waked, R ;
Behnia, M .
APPLIED THERMAL ENGINEERING, 2006, 26 (04) :382-395
[2]   Enhancing performance of wet cooling towers [J].
Al-Waked, Rafat ;
Behnia, Masud .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (10) :2638-2648
[3]   Experimental investigation on thermal performance of natural draft wet cooling towers employing an innovative wind-creator setup [J].
Alavi, Seyed Rashid ;
Rahmati, Mehdi .
ENERGY CONVERSION AND MANAGEMENT, 2016, 122 :504-514
[4]  
[Anonymous], 1962, Int. J. Heat Mass Transf.
[5]   Novel method for improving the cooling performance of natural draft wet cooling towers [J].
Chen, Xuehong ;
Sun, Fengzhong ;
Chen, Youliang ;
Gao, Ming .
APPLIED THERMAL ENGINEERING, 2019, 147 :562-570
[6]   Experimental research of the cross walls effect on the thermal performance of wet cooling towers under crosswind conditions [J].
Chen, Youliang ;
Sun, Fengzhong ;
Wang, Hongguo ;
Mu, Nasi ;
Gao, Ming .
APPLIED THERMAL ENGINEERING, 2011, 31 (17-18) :4007-4013
[7]   The transient start-up process of natural draft dry cooling towers in dispatchable thermal power plants [J].
Dong, Peixin ;
Li, Xiaoxiao ;
Guan, Zhiqiang ;
Gurgenci, Hal .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2018, 123 :201-212
[8]   Evaporative cooling of water in a natural draft cooling tower [J].
Fisenko, SP ;
Petruchik, AI ;
Solodukhin, AD .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2002, 45 (23) :4683-4694
[9]   Thermal performance analysis for high level water collecting wet cooling tower under crosswind conditions [J].
Gao, Ming ;
Zou, Jian ;
He, Suoying ;
Sun, Fengzhong .
APPLIED THERMAL ENGINEERING, 2018, 136 :568-575
[10]   Thermal Performance for Wet Cooling Tower with Different Layout Patterns of Fillings under Typical Crosswind Conditions [J].
Gao, Ming ;
Guo, Chang ;
Ma, Chaoqun ;
Shi, Yuetao ;
Sun, Fengzhong .
ENERGIES, 2017, 10 (01)