External heating of electrical cables and auto-ignition investigation

被引:49
作者
Courty, L. [1 ]
Garo, J. P. [2 ]
机构
[1] Univ Orleans, PRISME EA 4229, 63 Ave Lattre Tassigny, F-18020 Bourges, France
[2] Univ Poitiers, ENSMA, Inst P, UPR CNRS 3349, 1 Ave Clement Ader,Teleport 2,BP 40109, F-86961 Futuroscope, France
关键词
Electric cables; Flammability; Autoignition; Piloted ignition; FLAME; DEGRADATION; APPARATUS; TESTS; FTIR;
D O I
10.1016/j.jhazmat.2016.09.042
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Electric cables are now extensively used for both residential and industrial applications. During more than twenty years, multi-scale approaches have been developed to study fire behavior of such cables that represents a serious challenge. Cables are rather complicated materials because they consist of an insulated part and jacket of polymeric materials. These polymeric materials can have various chemical structures, thicknesses and additives and generally have a char-forming tendency when exposed to heat source. In this work, two test methods are used for the characterization of cable pyrolysis and flammability. The first one permits the investigation of cable pyrolysis. A description of the cable mass loss is obtained, coupling an Arrhenius expression with a 1D thermal model of cables heating. Numerical results are successfully compared with experimental data obtained for two types of cable commonly used in French nuclear power plants. The second one is devoted to ignition investigations (spontaneous or piloted) of these cables. All these basic observations, measurements and modelling efforts are of major interest for a more comprehensive fire resistance evaluation of electric cables. (C) 2016 Elsevier B.V. All rights reserved.
引用
收藏
页码:528 / 536
页数:9
相关论文
共 24 条
  • [1] Barnes MA., 1996, Fire Mater, V20, P17, DOI [10.1002/(SICI)1099-1018(199601)20:1andlt
  • [2] 17::AID-FAM554andgt
  • [3] 3.0.CO
  • [4] 2-C, DOI 10.1002/(SICI)1099-1018(199601)20:13.0.CO
  • [5] 2-C, 10.1002/(SICI)1099-1018, DOI 10.1002/(SICI)1099-1018]
  • [6] Thermal degradation of PVC cable insulation studied by simultaneous TG-FTIR and TG-EGA methods
    Benes, M
    Milanov, N
    Matuschek, G
    Kettrup, A
    Placek, V
    Balek, V
    [J]. JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2004, 78 (02) : 621 - 630
  • [7] COAKER AW, 1992, FIRE SAFETY J, V19, P19
  • [8] Characterization of the burning behavior and gaseous emissions of pine needles in a cone calorimeter - FTIR apparatus
    Fateh, Talal
    Richard, Franck
    Batiot, Benjamin
    Rogaume, Thomas
    Luche, Jocelyn
    Zaida, Justin
    [J]. FIRE SAFETY JOURNAL, 2016, 82 : 91 - 100
  • [9] Fernandez-Pello A. C., 1991, P 4 INT S FIR SAF SC, P237
  • [10] Investigating the burning characteristics of electric cables used in the nuclear power plant by way of 3-D transient FDS code
    Ferng, Y. M.
    Liu, C. H.
    [J]. NUCLEAR ENGINEERING AND DESIGN, 2011, 241 (01) : 88 - 94