From Entropy Generation to Exergy Efficiency at Varying Reference Environment Temperature: Case Study of an Air Handling Unit

被引:5
作者
Streckiene, Giedre [1 ]
Martinaitis, Vytautas [1 ]
Bielskus, Juozas [1 ]
机构
[1] Vilnius Gediminas Tech Univ, Dept Bldg Energet, Sauletekio Ave 11, LT-10223 Vilnius, Lithuania
关键词
heating; ventilation; and air conditioning (HVAC); air handling unit; energy efficiency; exergy efficiency; produced entropy; variable reference temperature; coenthalpy; HEAT-RECOVERY EXCHANGER; REFERENCE STATE; 2ND LAW; SYSTEMS; THERMODYNAMICS; ENERGY; VENTILATION; BUILDINGS;
D O I
10.3390/e21040361
中图分类号
O4 [物理学];
学科分类号
0702 ;
摘要
The continuous energy transformation processes in heating, ventilation, and air conditioning systems of buildings are responsible for 36% of global final energy consumption. Tighter thermal insulation requirements for buildings have significantly reduced heat transfer losses. Unfortunately, this has little effect on energy demand for ventilation. On the basis of the First and the Second Law of Thermodynamics, the concepts of entropy and exergy are applied to the analysis of ventilation air handling unit (AHU) with a heat pump, in this paper. This study aims to develop a consistent approach for this purpose, taking into account the variations of reference temperature and temperatures of working fluids. An analytical investigation on entropy generation and exergy analysis are used, when exergy is determined by calculating coenthalpies and evaluating exergy flows and their directions. The results show that each component of the AHU has its individual character of generated entropy, destroyed exergy, and exergy efficiency variation. However, the evaporator of the heat pump and fans have unabated quantities of exergy destruction. The exergy efficiency of AHU decreases from 45-55% to 12-15% when outdoor air temperature is within the range of -30 to +10 degrees C, respectively. This helps to determine the conditions and components of improving the exergy efficiency of the AHU at variable real-world local climate conditions. The presented methodological approach could be used in the dynamic modelling software and contribute to a wider application of the Second Law of Thermodynamics in practice.
引用
收藏
页数:21
相关论文
共 47 条
[1]   Heat transfer performance evaluation in circular tubes via internal repeated ribs with entropy and exergy analysis [J].
Ahmed, Sayed Ahmed E. Sayed ;
Ibrahim, Emad Z. ;
Ibrahim, Mostafa M. ;
Essa, Mohamed A. ;
Abdelatief, Mohamed A. ;
El-Sayed, Mohamed N. .
APPLIED THERMAL ENGINEERING, 2018, 144 :1056-1070
[2]  
Angelotti A., 2007, P 2 PALENC 28 AIVC C, VI, P59
[3]  
[Anonymous], 2018, 2018 GLOB STAT REP Z
[4]   A novel enhanced exergy method in analyzing HVAC system using soft computing approaches: A case study on mushroom growing hall [J].
Ardabili, Sina Faizollahzadeh ;
Najafi, Bahman ;
Ghaebi, Hadi ;
Shamshirband, Shahaboddin ;
Mostafaeipour, Ali .
JOURNAL OF BUILDING ENGINEERING, 2017, 13 :309-318
[5]   Effect of reference state characteristics on the Thermal Exergy analysis of a building [J].
Baldi, Marta Giulia ;
Leoncini, Lorenzo .
SUSTAINABILITY IN ENERGY AND BUILDINGS: PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE SEB-15, 2015, 83 :177-186
[6]   Thermodynamics today [J].
Bejan, Adrian .
ENERGY, 2018, 160 :1208-1219
[7]  
Bonetti V., 2017, P 9 EX EN ENV S SPLI, P924
[8]  
Borel L., 1984, THERMODYNAMIQUE ENER
[9]  
Borel L, 2010, Thermodynamics and energy systems analysis: from energy to exergy
[10]   Role of entropy generation minimization in thermal optimization [J].
Cheng, Xue-Tao ;
Liang, Xin-Gang .
CHINESE PHYSICS B, 2017, 26 (12)