Trading Energy Yield for Frequency Regulation: Optimal Control of Kinetic Energy in Wind Farms

被引:35
作者
De Rijcke, Simon [1 ]
Tielens, Pieter [1 ]
Rawn, Barry [1 ]
Van Hertem, Dirk [1 ]
Driesen, Johan [1 ]
机构
[1] Katholieke Univ Leuven, Dept ESAT, Res Grp Electa, B-3001 Heverlee, Belgium
关键词
Frequency regulation; maximum energy yield; optimization; smooth frequency variability; wind farm control;
D O I
10.1109/TPWRS.2014.2357684
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The burden on conventional units to regulate the system frequency increases if they are replaced due to wind farms. This paper explores up to which time scales the rotating kinetic energy in wind turbines can smooth frequency variations and assist with the regulation task. To this end, a comparison is made between a standard wind turbine controller and optimal control of wind turbines, respectively derived from causal time-domain simulations and an optimization algorithm that allows predicting. The latter algorithm is used to give a benchmark for the smoothing potential, shown by plotting the Pareto efficiency of the normalized standard deviation of frequency variability versus a normalized measure of the energy yield. Results indicate that smoothing comes with an energy loss that is determined by the energy content of power imbalances. It is shown that a wind share of 20%, within the instantaneous generation mix, can absorb frequency variations on timescales up to 100 sec while the energy loss is limited to only 2%. A higher share of wind power aggravates frequency variability. Nevertheless, in such circumstances the potential of rotating kinetic energy in wind farms increases.
引用
收藏
页码:2469 / 2478
页数:10
相关论文
共 24 条
[1]  
Ackermann T, 2005, WIND POWER IN POWER SYSTEMS, P1, DOI 10.1002/0470012684
[2]  
[Anonymous], 2011, DETERMINISTIC FREQUE
[3]  
[Anonymous], 2013, SUPP DOC NETW COD LO
[4]  
[Anonymous], 2001, IEEE POW ENG SOC SUM
[5]  
[Anonymous], 2010, PROC 9 INT WORKSHOP
[6]   Impacts of wind power minute-to-minute variations on power system operation [J].
Banakar, Hadi ;
Luo, Changling ;
Ooi, Boon Teck .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (01) :150-160
[7]   Enhancing Frequency Response Control by DFIGs in the High Wind Penetrated Power Systems [J].
Chang-Chien, Lee-Ren ;
Lin, Wei-Ting ;
Yin, Yao-Ching .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2011, 26 (02) :710-718
[8]   Participation of doubly fed induction wind generators in system frequency regulation [J].
de Almeida, Rogerio G. ;
Pecas Lopes, J. A. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) :944-950
[9]  
De Rijcke S., 2014, THESIS KU LEUVEN BEL
[10]   Centralised power control of wind farm, with doubly fed induction generators [J].
Hansen, AD ;
Sorensen, P ;
Iov, F ;
Blaabjerg, F .
RENEWABLE ENERGY, 2006, 31 (07) :935-951