Power angle control of grid-connected doubly fed induction generator wind turbines for fault ride-through

被引:29
|
作者
Bu, S. Qiqi [1 ]
Du, Wenjuan [2 ]
Wang, Haifeng F. [2 ]
Gao, S. [3 ]
机构
[1] Natl Grid TransCo, Wokingham RG41 5BN, England
[2] Brunel Univ, Sch Engn & Design, London, England
[3] Southeast Univ, Nanjing, Jiangsu, Peoples R China
关键词
LOW-VOLTAGE RIDE; CONTROL STRATEGY; DFIG; CAPABILITY;
D O I
10.1049/iet-rpg.2012.0130
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study proposes a power angle control strategy of grid-connected doubly fed induction generators (DFIGs) to improve the transient performance during grid fault ride-through (FRT). The proposed power angle control can efficiently restrict the rotor-side current under a limited converter rating, support the terminal voltage of DFIGs and hence improve system stability during the fault period. In this study, the power angle of DFIGs in a multi-machine power system is defined firstly and then the relation between the defined power angle and rotor-side current surge and terminal voltage dip of DFIGs are analysed, respectively. Based on the analysis, control of DFIG power angle is implemented expediently on the existing flux magnitude and angle control (FMAC) scheme of DFIGs as an improved FMAC scheme. In this study, two test examples are presented to demonstrate and validate the effectiveness of improved FMAC with power angle control and to compare it with the conventional PQdq control and FMAC. Simulation results show that it can significantly enhance the FRT capability of grid-connected DFIGs.
引用
收藏
页码:18 / 27
页数:10
相关论文
共 50 条
  • [1] A comprehensive review of fault ride-through capability of wind turbines with grid-connected doubly fed induction generator
    Parameswari, G. Angala
    Sait, H. Habeebullah
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2020, 30 (08):
  • [2] Control of a doubly fed induction generator in a wind turbine during grid fault ride-through
    Ran, Li
    Xiang, Dawei
    Tavner, Peter J.
    Yang, Shunchang
    2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 1623 - 1623
  • [3] Control of a doubly fed induction generator in a wind turbine during grid fault ride-through
    Xiang, Dawei
    Ran, Li
    Tavner, Peter J.
    Yang, Shunchang
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2006, 21 (03) : 652 - 662
  • [4] Grid-fault ride-through analysis and control of wind turbines with doubly fed induction generators
    Rahimi, Mohsen
    Parniani, Mostafa
    ELECTRIC POWER SYSTEMS RESEARCH, 2010, 80 (02) : 184 - 195
  • [5] Ride-through control strategy of a doubly fed induction generator for symmetrical grid fault
    Xiang, Da-Wei
    Yang, Shun-Chang
    Ran, Li
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2006, 26 (03): : 164 - 170
  • [6] An improved fault ride-through strategy for doubly fed induction generator-based wind turbines
    Kasem, A. H.
    El-Saadany, E. F.
    El-Tamaly, H. H.
    Wahab, M. A. A.
    IET RENEWABLE POWER GENERATION, 2008, 2 (04) : 201 - 214
  • [7] Fault ride-through performance of wind turbine with doubly fed induction generator
    Zou, Heping
    Sun, Hui
    Zou, Jiyan
    ICIEA 2007: 2ND IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS, VOLS 1-4, PROCEEDINGS, 2007, : 1607 - 1611
  • [8] System simulation of a doubly fed induction generator ride-through control for symmetrical grid fault
    School of Electrical Engineering, University of Chongqing, Chongqing 400044, China
    不详
    Zhongguo Dianji Gongcheng Xuebao, 2006, 10 (130-135):
  • [9] The fault ride through technologies for doubly fed induction generator wind turbines
    Ling, Yu
    WIND ENGINEERING, 2016, 40 (01) : 31 - 49
  • [10] Doubly Fed Induction Generator Wind Farm Fault ride-through capability
    Hilal, Mohamed
    Errami, Youssef
    Benchagra, Mohamed
    Maaroufi, Mohamed
    Cherkaoui, Mohamed
    Ouassaid, Mohammed
    2012 INTERNATIONAL CONFERENCE ON MULTIMEDIA COMPUTING AND SYSTEMS (ICMCS), 2012, : 1079 - 1082