Research of Hydro-Turbine Governor Supplementary Control Strategy for Islanding AC Grid at Sending Terminal of HVDC System

被引:17
作者
Zhang, Guangtao [1 ]
Cheng, Yuanchu [1 ]
Lu, Na [2 ]
Guo, Qi [3 ]
机构
[1] Wuhan Univ, Dept Power & Mech Engn, Wuhan 430072, Peoples R China
[2] Northwest A&F Univ, Coll Water Resources & Architectural Engn, Yangling 712100, Peoples R China
[3] Southern Grid Co Ltd, Technol Res Ctr China, Guangzhou 510623, Guangdong, Peoples R China
基金
中国国家自然科学基金;
关键词
Governor; hydro islanding system; high voltage direct current (HVDC); islanding frequency control; TRANSMISSION; OPERATION;
D O I
10.1109/TEC.2016.2561958
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The occurrence of the high voltage direct current (HVDC) system fault often results in adverse effect on the stability of nearby connected ac grid. To avoid such effect, many HVDC transmission projects with sending terminal mainly composed of one or more giant hydropower stations chose islanding operation mode as one of its normal operation modes. However, in that case, once bipolar blocking caused by HVDC system fault occurs, the amount of power transmission will drop dramatically and two problems of the islanding ac system will emerge: 1) some of the units will stabilize into motor mode; 2) system stable frequency will become much higher than the normal value. To solve these problems, combining with practical engineering, reasons of them are analyzed first, then supplementary control strategy of hydro-turbine governor is proposed in this paper. Results of the simulation and field test showed that the strategy proposed in this paper can effectively avoid the occurrence of the two problems. Consequently, the supplementary control strategy is beneficial to the fault recovery and restarting of the HVDC system, and can also enhance the safety running level of the hydro-turbine units and grid connected.
引用
收藏
页码:1229 / 1238
页数:10
相关论文
共 29 条
  • [1] [Anonymous], 2012, POW SYST US MAN, P11
  • [2] [Anonymous], 2000, MODERN CONTROL ENG
  • [3] [Anonymous], 2009, HVDC TRANSMISSION PO, DOI DOI 10.1002/9780470822975
  • [4] Archer BA, 2002, IEEE CCEC 2002: CANADIAN CONFERENCE ON ELECTRCIAL AND COMPUTER ENGINEERING, VOLS 1-3, CONFERENCE PROCEEDINGS, P60, DOI 10.1109/CCECE.2002.1015175
  • [5] Arrillaga J., 2007, Flexible Power Transmission. The HVDC Options
  • [6] Asplund G, 2004, 2004 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1 AND 2, P2299
  • [7] The ABCs of HVDC transmission technologies
    Bahrman, Michael P.
    Johnson, Brian K.
    [J]. IEEE POWER & ENERGY MAGAZINE, 2007, 5 (02): : 32 - 44
  • [8] Control for Grid-Connected and Intentional Islanding Operations of Distributed Power Generation
    Balaguer, Irvin J.
    Lei, Qin
    Yang, Shuitao
    Supatti, Uthane
    Peng, Fang Zheng
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (01) : 147 - 157
  • [9] Bennett M. G., 2012, SURVEY RELIABILITY H
  • [10] Benysek G., 2008, POWER ELECT SMART EL