A Novel Sensor Platform Matching the Improved Version of IPMVP Option C for Measuring Energy Savings

被引:10
作者
Tseng, Yen-Chieh [1 ]
Lee, Da-Sheng [2 ]
Lin, Cheng-Fang [1 ]
Chang, Ching-Yuan [1 ]
机构
[1] Natl Taiwan Univ, Grad Inst Environm Engn, Taipei 10617, Taiwan
[2] Natl Taipei Univ Technol, Dept Energy & Refrigerating Air Conditioning Engn, Taipei 106, Taiwan
关键词
sensor platform; IPMVP; energy savings; EPC global architecture framework; vertical garden system (VGS); environmental monitoring; BUILDINGS;
D O I
10.3390/s130506811
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
It is easy to measure energy consumption with a power meter. However, energy savings cannot be directly computed by the powers measured using existing power meter technologies, since the power consumption only reflects parts of the real energy flows. The International Performance Measurement and Verification Protocol (IPMVP) was proposed by the Efficiency Valuation Organization (EVO) to quantify energy savings using four different methodologies of A, B, C and D. Although energy savings can be estimated following the IPMVP, there are limitations on its practical implementation. Moreover, the data processing methods of the four IPMVP alternatives use multiple sensors (thermometer, hygrometer, Occupant information) and power meter readings to simulate all facilities, in order to determine an energy usage benchmark and the energy savings. This study proposes a simple sensor platform to measure energy savings. Using usually the Electronic Product Code (EPC) global standard, an architecture framework for an information system is constructed that integrates sensors data, power meter readings and occupancy conditions. The proposed sensor platform is used to monitor a building with a newly built vertical garden system (VGS). A VGS shields solar radiation and saves on energy that would be expended on air-conditioning. With this platform, the amount of energy saved in the whole facility is measured and reported in real-time. The data are compared with those obtained from detailed measurement and verification (M&V) processes. The discrepancy is less than 1.565%. Using measurements from the proposed sensor platform, the energy savings for the entire facility are quantified, with a resolution of +/- 1.2%. The VGS gives an 8.483% daily electricity saving for the building. Thus, the results show that the simple sensor platform proposed by this study is more widely applicable than the four complicated IPMVP alternatives and the VGS is an effective tool in reducing the carbon footprint of a building.
引用
收藏
页码:6811 / 6831
页数:21
相关论文
共 17 条
[1]   A survey on sensor networks [J].
Akyildiz, IF ;
Su, WL ;
Sankarasubramaniam, Y ;
Cayirci, E .
IEEE COMMUNICATIONS MAGAZINE, 2002, 40 (08) :102-114
[2]  
[Anonymous], 1996, N AM EN MEAS VER PRO
[3]  
Armenio Felice., 2007, The EPCglobal Architecture Framework
[4]  
Bureau of Energy, MOEA AN EN SUPPL DEM
[5]   Energy Saving Effects of Wireless Sensor Networks: A Case Study of Convenience Stores in Taiwan [J].
Chen, Chih-Sheng ;
Lee, Da-Sheng .
SENSORS, 2011, 11 (02) :2013-2034
[6]  
Estrin D., 1999, MobiCom'99. Proceedings of Fifth Annual ACM/IEEE International Conference on Mobile Computing and Networking, P263, DOI 10.1145/313451.313556
[7]   Response of conventional and energy-saving buildings to design and human dependent factors [J].
Filippín, C ;
Larsen, SF ;
Beascochea, A ;
Lesino, G .
SOLAR ENERGY, 2005, 78 (03) :455-470
[8]   Routing Protocols in Wireless Sensor Networks [J].
Garcia Villalba, Luis Javier ;
Sandoval Orozco, Ana Lucila ;
Trivino Cabrera, Alicia ;
Barenco Abbas, Claudia Jacy .
SENSORS, 2009, 9 (11) :8399-8421
[9]  
Gholamzadeh B.N.H., 2008, WORLD ACAD SCI ENG T, V45, P560
[10]   Retro and on-going commissioning tool applied to an existing building: Operability and results of IPMVP [J].
Ginestet, S. ;
Marchio, D. .
ENERGY, 2010, 35 (04) :1717-1723