The method of determining the insulation parameters in three-phase electrical networks with isolated neutral with voltages up to and above 1000 V

被引:3
作者
Utegulov, B. B. [1 ]
机构
[1] S Seifullin Kazakh Agrotech Univ, Dept Energy, 62 Pobeda Ave, Astana, Kazakhstan
来源
2016 INTERNATIONAL CONFERENCE ON NEW ENERGY AND FUTURE ENERGY SYSTEM (NEFES 2016) | 2016年 / 40卷
关键词
D O I
10.1088/1755-1315/40/1/012024
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In work the new method of definition of isolation's parameters in a three-phase symmetric electrical network with isolated neutral which is based on measurement of modules sizes of a linear voltage, voltages of phases. and A concerning to ground, after connection of active additional conductivity between phase A of electrical network and ground is shown and the analysis of a blunder of the developed method is made. The analysis of a blunder has shown, that the developed method provides satisfactory accuracy at definition of isolation's parameters, and also simplicity and the safety of operations in working electro installations of up to above 1000 V voltage.