Natural ventilation of an isolated generic building with a windward window and different windexchangers: CFD validation, sensitivity study and performance analysis

被引:24
作者
Antonio Castillo, J. [1 ]
Huelsz, Guadalupe [2 ]
van Hooff, Twan [3 ,4 ]
Blocken, Bert [3 ,4 ]
机构
[1] Univ Nacl Autonoma Mexico, Ctr Invest Arquitectura Urbanismo & Paisaje, Fac Arquitectura, Av Univ 3000, Mexico City 04510, DF, Mexico
[2] Univ Nacl Autonoma Mexico, Inst Energias Renovables, Temixco 62580, Morelos, Mexico
[3] Eindhoven Univ Technol, Dept Built Environm, Bldg Phys & Serv, POB 513, NL-5600 MB Eindhoven, Netherlands
[4] Katholieke Univ Leuven, Dept Civil Engn, Bldg Phys Sect, Kasteelpk Arenberg 40,Bus 2447, B-3001 Leuven, Belgium
关键词
windexchanger; windcatcher; natural ventilation; CFD; validation; ATMOSPHERIC BOUNDARY-LAYER; CROSS-VENTILATION; TURBULENCE MODELS; FLOW; IMPACT; SIMULATION; CATCHER; ENVIRONMENT; PREDICTION; GEOMETRY;
D O I
10.1007/s12273-018-0502-4
中图分类号
O414.1 [热力学];
学科分类号
摘要
Windexchangers are relatively small structures located on the building rooftop to promote natural ventilation. This paper presents a Computational Fluid Dynamics (CFD) validation study, sensitivity analysis and performance comparison of three windexchanger (WE) configurations applied to a generic isolated building with a windward window. The study is limited to wind-driven (isothermal) ventilation, for wind perpendicular to the windward facade. The CFD simulations are based on the 3D-steady Reynolds-Averaged Navier-Stokes (RANS) equations. The validation study is performed with experimental results from a previously published water channel test. The sensitivity analysis focuses on the domain size, grid resolution and turbulence model. The performance evaluation of the three WE configurations is based on the mean velocity and mean static pressure coefficients in the vertical centerplane, the ventilation volume flow rate and the volume percentage of the living zone with air speed ratio equal to or above 0.10. The WE configuration with four openings and one duct shows the highest ventilation flow rate (0.232 m(3)/s) and the highest volume percentage (21%). This study shows that the assessment and selection of WE configurations should not only be based on volume flow rate or ACH but should consider the living zone air speed ratio as well, specifically concerning the flow distribution in the living zone.
引用
收藏
页码:475 / 488
页数:14
相关论文
共 61 条
[1]  
[Anonymous], 2014, J WIND ENG IND AEROD
[2]  
[Anonymous], 2013, FLUENT 15 US GUID
[3]   Wind engineering - Past, present and future [J].
Baker, C. J. .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2007, 95 (9-11) :843-870
[4]   Flow visualization, PIV measurement and CFD calculation for fluid-driven natural cross-ventilation in a scale model [J].
Bangalee, M. Z. I. ;
Miau, J. J. ;
Lin, S. Y. ;
Yang, J. H. .
ENERGY AND BUILDINGS, 2013, 66 :306-314
[5]   Analysis and validation of the methodology used in the extrapolation of wind speed data at different heights [J].
Banuelos-Ruedas, F. ;
Angeles-Camacho, C. ;
Rios-Marcuello, S. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2010, 14 (08) :2383-2391
[6]  
Barlow J. B., 1999, Low-speed wind tunnel testing, V3rd ed.
[7]   Wind environmental conditions in passages between two long narrow perpendicular buildings [J].
Blocken, B. ;
Stathopoulos, T. ;
Carmeliet, J. .
JOURNAL OF AEROSPACE ENGINEERING, 2008, 21 (04) :280-287
[8]   Computational analysis of the performance of a venturi-shaped roof for natural ventilation: Venturi-effect versus wind-blocking effect [J].
Blocken, B. ;
van Hooff, T. ;
Aanen, L. ;
Bronsema, B. .
COMPUTERS & FLUIDS, 2011, 48 (01) :202-213
[9]   CFD evaluation of wind speed conditions in passages between parallel buildings - effect of wall-function roughness modifications for the atmospheric boundary layer flow [J].
Blocken, Bert ;
Carmeliet, Jan ;
Stathopoulos, Ted .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2007, 95 (9-11) :941-962
[10]   CFD simulation of the atmospheric boundary layer: wall function problems [J].
Blocken, Bert ;
Stathopoulos, Ted ;
Carmeliet, Jan .
ATMOSPHERIC ENVIRONMENT, 2007, 41 (02) :238-252