Development of a numerical model for the simulation of vertical U-tube ground heat exchangers

被引:143
|
作者
Li, Zhongjian [1 ]
Zheng, Maoyu [1 ]
机构
[1] Harbin Inst Technol, Sch Civil & Environm Engn, Harbin 150090, Peoples R China
关键词
Geothermal energy utilization systems; Vertical U-tube ground heat exchangers; Three-dimensional numerical simulation; Experimental verification; FLOW;
D O I
10.1016/j.applthermaleng.2008.04.024
中图分类号
O414.1 [热力学];
学科分类号
摘要
Vertical U-tube ground heat exchangers are a key component in geothermal energy utilization systems like ground source heat pumps (GSHPs). This paper presents a three-dimensional unstructured finite volume model for them. The model uses Delaunay triangulation method to mesh the cross-section domain of the borefield (borehole field), and consequently may intactly retain the geometric structure in the borehole. To further improve the computational accuracy, the soil is divided into many layers in the vertical direction in order to account for the effect of changing fluid temperature with depth on the thermal process in the borefield. The inlet temperature of the ground heat exchanger (GHE) is used as a boundary condition, and the inside and outside surfaces of the U-tube pipes are treated as the conjugated interfaces in the domain. Thus, the conjugate thermal processes between the fluid in the pipes and the soil around it and between the two pipe legs may be accounted fully. A comparison of the model predictions and experimental data shows that the model has good prediction accuracy. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:920 / 924
页数:5
相关论文
共 50 条
  • [41] U-Tube Diameter Dependence of Heat Output for Borehole Heat Exchangers
    Dai, Chuanshan
    Wang, Shuai
    Qin, Weixing
    PROGRESS IN CIVIL ENGINEERING, PTS 1-4, 2012, 170-173 : 2613 - +
  • [42] An Improved Thermal-Resistance-Capacitance Model for Vertical Single U-Tube Ground Heat Exchanger
    Liao, Quan
    Fan, Yongxiang
    Zhu, Xiaobo
    Li, Jintang
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2019, 11 (01)
  • [43] Techno-economic analysis of single U-tube and double U-tube heat exchangers in Chongqing area
    Wang Yong
    Guo Kai-sheng
    Tian Rong
    Han Chuan-pu
    Lai Dao-xin
    Xu Feng
    JOURNAL OF CENTRAL SOUTH UNIVERSITY OF TECHNOLOGY, 2009, 16 : 244 - 248
  • [44] Explicit Multipole Formulas for Calculating Thermal Resistance of Single U-Tube Ground Heat Exchangers
    Claesson, Johan
    Javed, Saqib
    ENERGIES, 2018, 11 (01):
  • [45] Thermodynamic optimization of ground heat exchangers with single U-tube by entropy generation minimization method
    Li, Min
    Lai, Alvin C. K.
    ENERGY CONVERSION AND MANAGEMENT, 2013, 65 : 133 - 139
  • [46] Techno-economic analysis of single U-tube and double U-tube heat exchangers in Chongqing area
    王勇
    郭凯生
    田荣
    韩传璞
    赖道新
    徐峰
    Journal of Central South University, 2009, 16 (S1) : 244 - 248
  • [47] Techno-economic analysis of single U-tube and double U-tube heat exchangers in Chongqing area
    王勇
    郭凯生
    田荣
    韩传璞
    赖道新
    徐峰
    JournalofCentralSouthUniversityofTechnology, 2009, 16(S1) (S1) : 244 - 248
  • [48] Study on the efficiency of single and double U-tube heat exchangers
    Fang, Liang
    Diao, Nairen
    Fang, Zhaohong
    Zhu, Ke
    Zhang, Wenke
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 4045 - 4051
  • [49] Operation Analyse of a U-tube Ground Heat Exchangers of GSHP system in Cold Region of China
    Li, Huai
    Wu, Jianlin
    Yu, Zhen
    Xu, Wei
    6TH INTERNATIONAL BUILDING PHYSICS CONFERENCE (IBPC 2015), 2015, 78 : 1937 - 1943
  • [50] Study on heat transfer model of vertical u tube ground heat exchangers based on line heat source theory