Effects of Household Battery Systems on LV Residential Feeder Voltage Management

被引:10
作者
Ahmed, Moudud [1 ]
Ganeshan, Anima [1 ]
Amani, Ali Moradi [1 ]
Al Khafaf, Namer [1 ]
Nutkani, Inam Ullah [1 ]
Vahidnia, Arash [1 ]
Jalili, Mahdi [1 ]
Hasan, Kazi [1 ]
Datta, Manoj [1 ]
Razzaghi, Reza [2 ]
McGrath, Brendan [1 ]
Meegahapola, Lasantha [1 ]
机构
[1] RMIT Univ, Sch Engn, Melbourne, Vic 3000, Australia
[2] Monash Univ, Dept Elect & Comp Syst Engn, Clayton, Vic 3800, Australia
关键词
Battery energy storage system (BESS); low-voltage network; overvoltage; smart meter data; solar-PV; undervoltage; voltage unbalance; DISTRIBUTION NETWORKS; STORAGE-SYSTEMS; DISTRIBUTION GRIDS; HOSTING CAPACITY; REACTIVE POWER; PV; OPTIMIZATION; PROPAGATION; UNBALANCE; EMISSION;
D O I
10.1109/TPWRD.2022.3176099
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
With the advancements of the battery energy storage systems (BESSs), reduction of their manufacturing costs and government subsidies, the BESS uptake is likely to increase rapidly in power distribution networks. This paper investigates the effects of residential BESSs on low-voltage (LV) networks using the actual household load profiles equipped with BESS and solar-photovoltaic (PV) systems. The electricity consumption data collected via smart meters (2200 households with PV/BESS, 1950 households with PV only and 1000 households without a PV or a BESS) at different solar-PV penetration levels and network types are used to simulate real network operating scenarios. A real LV distribution network in Australia is analysed in DIgSILENT PowerFactory under different scenarios, such as, customers with and without a solar-PV/BESS, with a solar-PV but without a BESS, and without a solar-PV, by using both the power flow and quasi-dynamic simulation studies under balanced and the unbalanced network loading conditions. According to the study, customers experience large voltage excursions from solar-PV power exports, which could be resolved by the household BESS, provided that the BESS charging is coordinated with the solar-PV production. Moreover, quasi-dynamic simulation shows that the BESS could reduce the violation of the over-voltage limit during the solar peak hours (midday) by lowering the worst-case feeder voltage by 3%. Finally, extreme-event (high solar PV generation scenario) simulation shows that the implementation of the BESS controller to facilitate charging BESS during afternoon solar-PV export may reduce the negative grid impact and will assist to avoid network upgrades.
引用
收藏
页码:5325 / 5336
页数:12
相关论文
共 35 条
[1]  
Agnew S., 2018, THESIS U QUEENSLAND
[2]   Mitigation of Rooftop Solar PV Impacts and Evening Peak Support by Managing Available Capacity of Distributed Energy Storage Systems [J].
Alam, M. J. E. ;
Muttaqi, K. M. ;
Sutanto, D. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (04) :3874-3884
[3]  
Alan M., 2012, PROC IEEE POWER ENER, P1
[4]  
Brinsmead T., 2015, Future energy storage trends: An assessment of the economic viability, potential uptake and impacts of electrical energy storage on the NEM 2015-2035
[5]  
C. E. Council, 2020, CLEAN EN COUNC
[6]   Analysis of Voltage Profile Problems Due to the Penetration of Distributed Generation in Low-Voltage Secondary Distribution Networks [J].
Chen, Po-Chen ;
Salcedo, Reynaldo ;
Zhu, Qingcheng ;
de Leon, Francisco ;
Czarkowski, Dariusz ;
Jiang, Zhong-Ping ;
Spitsa, Vitaly ;
Zabar, Zivan ;
Uosef, Resk Ebrahem .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (04) :2020-2028
[7]  
Electromagnetic compatibility (EMC), 2008, 610003132008 IEC, P3
[8]   A two-level over-voltage control strategy in distribution networks with high PV penetration [J].
Emarati, Mohammadreza ;
Barani, Mostafa ;
Farahmand, Hossein ;
Aghaei, Jamshid ;
del Granado, Pedro Crespo .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 130
[9]   Bottom-up modeling of residential batteries and their effect on system-level generation cost [J].
Jaglal, Dillon ;
Procopiou, Andreas T. ;
Petrou, Kyriacos ;
Ochoa, Luis F. .
ELECTRIC POWER SYSTEMS RESEARCH, 2020, 189
[10]   Optimal Operation of Distributed Energy Storage Systems to Improve Distribution Network Load and Generation Hosting Capability [J].
Jayasekara, Nadeeshani ;
Masoum, Mohammad A. S. ;
Wolfs, Peter J. .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2016, 7 (01) :250-261