POTENTIAL-FLOW MODELING FOR DATA CENTER APPLICATIONS

被引:0
作者
Healey, Christopher M. [1 ]
VanGilder, James W. [1 ]
Sheffer, Zachary R. [2 ]
Zhang, Xuanhang [1 ]
机构
[1] APC Schneider Elect, Billerica, MA 01862 USA
[2] Northeastern Univ, Boston, MA USA
来源
PROCEEDINGS OF THE ASME PACIFIC RIM TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC SYSTEMS, MEMS AND NEMS 2011, VOL 2 | 2012年
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Potential-flow-based airflow and heat transfer models have been proposed as a computationally efficient alternative to the Navier-Stokes Equations for predicting the three-dimensional flow field in data center applications. These models are simple, solve quickly, and capture much of the fluid flow physics, but ignore buoyancy and frictional effects, i.e., rotationality, turbulence, and wall friction. However, a comprehensive comparison of the efficiency and accuracy of these methods versus more sophisticated tools, like CFD, is lacking. The main contribution of this paper is a study of the performance of potential-flow methods compared to CFD in eight layouts inspired by actual data center configurations. We demonstrate that potential-flow methods can be helpful in data center design and management applications.
引用
收藏
页码:527 / +
页数:3
相关论文
共 15 条
[1]  
[Anonymous], FLOV V9 1 SOFTW MAN
[2]  
ASHRAE, 2008, THERM GUID DAT PROC, V2nd
[3]  
Bash C., 2009, P IMECE NOV 13 19 LA
[4]  
Ferziger J.H., 2002, Computational methods for fluid dynamics, Vthird
[5]  
Hamann H., 2010, P ITHERM JUN 2 5 LAS
[6]  
Hamann H., 2010, P ITHERM JUN 2 5 LAS
[7]  
Iyengar M., 2007, P IPACK JUL 8 12 VAN
[8]  
Patel C., 2001, P IPACK JUL 8 13 KAU
[9]  
Shrivastava S., 2006, P ITHERM MAY 31 JUN
[10]  
VanGilder J., 2011, P IPACK JUL 6 8 PORT