The sharing of responsibility between the supplier and the consumer for harmonic voltage distortion: A case study

被引:31
作者
de Paula Silva, Sergio Ferreira [1 ]
de Oliveira, Jose Carlos [1 ]
机构
[1] Univ Fed Uberlandia, Fac Engn Elet, BR-38400902 Uberlandia, MG, Brazil
关键词
harmonic distortion; harmonic direction; power quality; sharing harmonic responsibility; load modeling; standards;
D O I
10.1016/j.epsr.2008.04.003
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The aim of this research paper is to demonstrate the application of a proposed procedure for the sharing of responsibility between the supplier and the consumer for the actual harmonic voltage distortion at a given point of common coupling (PCC). The methodology is based on the analysis of measured voltage and current signals at the PCC and on information related to the harmonic impedances involved in the process. Both the supply and the load impedances are considered and an approach for coupling these with a consumer representative load is presented. The method is applied to a real commercial installation containing a combination of linear and nonlinear components fed by a pre-distorted 13.8 kV busbar. The result emphasizes the consistence of the approach in identifying the individual contributions of the supplier and the consumer. By finding the supply and load harmonic contributions, it is possible to achieve fairer cost sharing when mitigation procedures are needed to reduce voltage distortion to admissible legislation limits. (C) 2008 Elsevier B.V. All rights reserved.
引用
收藏
页码:1959 / 1964
页数:6
相关论文
共 10 条
[1]  
[Anonymous], 5191992 IEEE
[2]  
El Arini MMM, 1998, INT C HARMON QUAL PO, P930, DOI 10.1109/ICHQP.1998.760167
[3]  
*EN, 1999, 501601999 EN
[4]  
MAKRAM REB, 1993, P 25 SE S SYST THEOR, P124
[5]  
MOUSTAFA AA, 1996, P 9 INT C HARM QUAL
[6]  
*RMS EL SYST, NETW AN MARH 2U HARM
[7]  
Soliman SA, 1996, IEEE MEDITERR ELECT, P1615, DOI 10.1109/MELCON.1996.551262
[8]   Conforming and non-conforming current for attributing steady state power quality problems [J].
Srinivasan, K ;
Jutras, R .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (01) :212-217
[9]   A NEW METHOD OF HARMONIC POWER DETECTION BASED ON THE INSTANTANEOUS ACTIVE POWER IN 3-PHASE CIRCUITS [J].
TANAKA, T ;
AKAGI, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (04) :1737-1742
[10]   A method for determining customer and utility harmonic contributions at the point of common coupling [J].
Xu, WS ;
Liu, YL .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (02) :804-811