Life cycle analysis of enhanced condenser features for air-cooled chillers serving air-conditioned buildings

被引:9
|
作者
Yu, FW [1 ]
Chan, KT [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
关键词
air-cooled chiller; condensing temperature control; evaporative pre-coolers; life cycle analysis; variable speed condenser fans;
D O I
10.1016/j.buildenv.2005.04.018
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Air-cooled chillers are commonly used to provide cooling energy for air-conditioned buildings at the expense of considerable electricity. This paper examines the life cycle electricity cost of these chillers with the improved condenser features of condensing temperature control (CTC), evaporative pre-coolers (EC) and variable speed condenser fans (VSF). A validated model for an air-cooled screw chiller was used to ascertain how the individual and mixed features influence the annual electricity consumption of chillers in various operating conditions. It is estimated that the life cycle electricity cost savings range from HKS 2,099,742 with EC to HK$6,399,564 with all the three features, with regard to a chiller plant serving an office building for 15 yr. The life cycle analysis reported here provides important insights into how to reap the benefits of energy efficient technologies for air-cooled chillers. (C) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:981 / 991
页数:11
相关论文
共 50 条
  • [1] Economic benefits of improved condenser features for air-cooled chillers serving an air-conditioned hotel
    Yu, FW
    Chan, KT
    APPLIED THERMAL ENGINEERING, 2006, 26 (10) : 1063 - 1073
  • [2] An alternative approach for the performance rating of air-cooled chillers used in air-conditioned buildings
    Yu, F. W.
    Chan, K. T.
    BUILDING AND ENVIRONMENT, 2006, 41 (12) : 1723 - 1730
  • [3] Low-energy design for air-cooled chiller plants in air-conditioned buildings
    Yu, FW
    Chan, KT
    ENERGY AND BUILDINGS, 2006, 38 (04) : 334 - 339
  • [4] Optimum condenser fan staging for air-cooled chillers
    Yu, FW
    Chan, KT
    APPLIED THERMAL ENGINEERING, 2005, 25 (14-15) : 2204 - 2218
  • [5] Optimizing condenser fan control for air-cooled centrifugal chillers
    Yu, F. W.
    Chan, K. T.
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2008, 47 (07) : 942 - 953
  • [6] Energy performance of air-cooled chillers with sprayed water on condenser
    Lu, Jian
    Ren, Shengfeng
    Yang, Junlan
    Chang, Ru
    Shen, Zheng
    Yang, Hongxing
    FIRST INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT, PROCEEDINGS VOLS 1-3, 2008, : 355 - 362
  • [7] Improved condenser design and condenser-fan operation for air-cooled chillers
    Yu, FW
    Chan, KT
    APPLIED ENERGY, 2006, 83 (06) : 628 - 648
  • [8] A STUDY ON AIR-COOLED CHILLERS WITH EVAPORATIVELY COOLED CONDENSER FOR 3 TYPES OF CLIMATE
    Kocak Soylu, Sezgi
    Atmaca, Ibrahim
    ISI BILIMI VE TEKNIGI DERGISI-JOURNAL OF THERMAL SCIENCE AND TECHNOLOGY, 2016, 36 (01) : 1 - 8
  • [9] Enhanced performance of air-cooled chillers using evaporative cooling
    Huan, Z.
    Shijun, Y.
    Hongxing, Y.
    Jianlei, N.
    Building Services Engineering Research and Technology, 2000, 21 (04) : 213 - 217
  • [10] Critique of the design and operation of sustainable air-cooled chillers in commercial buildings
    Yu, F.W.
    Chan, K.T.
    Sit, R.K.Y.
    Yang, J.
    Energy Engineering: Journal of the Association of Energy Engineering, 2015, 112 (03): : 55 - 79