Transient analysis based determination of derating factor for earth air tunnel heat exchanger in summer

被引:29
作者
Misra, Rohit [1 ]
Bansal, Vikas [2 ]
Das Agrawal, Ghanshyam [1 ]
Mathur, Jyotirmay [1 ]
Aseri, Tarun [3 ]
机构
[1] Malaviya Natl Inst Technol, Dept Mech Engn, Jaipur, Rajasthan, India
[2] Govt Women Engn Coll, Ajmer, India
[3] Govt Engn Coll, Ajmer, India
关键词
Earth air tunnel heat exchanger; Performance deterioration; Derating factor; Transient analysis; PERFORMANCE ANALYSIS; ENERGY-CONSERVATION; ANALYTICAL-MODEL; COOLING SYSTEM; SOIL; BUILDINGS; PREDICT;
D O I
10.1016/j.enbuild.2012.11.001
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Thermal performance of earth air tunnel heat exchanger (BATHE) under transient operating conditions has been evaluated for predominantly hot and dry climate of Ajmer (India) using experimental and computational fluid dynamics modeling. Effect of time duration of continuous operation and thermal conductivity of soil on thermal performance of EATHE under transient conditions has been analyzed. Results show that the transient thermal performance of EATHE is significantly dependent on thermal conductivity of the soil and duration of its continuous operation. Under steady state condition, a drop of 18.8 degrees C is obtained in air passing through BATHE having 0.1 m diameter and 60 m length, at 5 m s(-1) flow velocity, whereas, the transient analysis shows that for soil having thermal conductivity of 0.52 Wm(-1) K-1, the cooling of air reduces from 18.7 degrees C to 16.6 degrees C, after 24 h of continuous operation. Change in cooling effect after 24h of operation for soil thermal conductivity of 2.0 W m(-1) K-1 and 4.0 W m(-1) K-1, reduced from 18.8 degrees C to 18.5 degrees C and 18.8 degrees C to 18.7 degrees C respectively. The analyzed cases have shown the range of derating to be as minimal as 0% to as high as 64%, which if ignored while designing may lead to poor performance of earth air heat exchangers. (C) 2012 Elsevier B.V. All rights reserved.
引用
收藏
页码:103 / 110
页数:8
相关论文
共 20 条
[1]   ON THE USE OF THE ATMOSPHERIC HEAT SINKS FOR HEAT DISSIPATION [J].
AGAS, G ;
MATSAGGOS, T ;
SANTAMOURIS, M ;
ARGYRIOU, A .
ENERGY AND BUILDINGS, 1991, 17 (04) :321-329
[2]   Simple and accurate model for the ground heat exchanger of a passive house [J].
Badescu, Viorel .
RENEWABLE ENERGY, 2007, 32 (05) :845-855
[3]   Performance analysis of integrated earth-air-tunnel-evaporative cooling system in hot and dry climate [J].
Bansal, Vikas ;
Mishra, Rohit ;
Das Agarwal, Ghanshyam ;
Mathur, Jyotirmay .
ENERGY AND BUILDINGS, 2012, 47 :525-532
[4]   Performance analysis of earth-pipe-air heat exchanger for summer cooling [J].
Bansal, Vikas ;
Misra, Rohit ;
Das Agrawal, Ghanshyam ;
Mathur, Jyotirmay .
ENERGY AND BUILDINGS, 2010, 42 (05) :645-648
[5]   Performance analysis of earth-pipe-air heat exchanger for winter heating [J].
Bansal, Vikas ;
Misra, Rohit ;
Das Agrawal, Ghanshyam ;
Mathur, Jyotirmay .
ENERGY AND BUILDINGS, 2009, 41 (11) :1151-1154
[6]   Energy from a two-pipe, earth-to-air heat exchanger [J].
Bojic, M ;
Papadakis, G ;
Kyritsis, S .
ENERGY, 1999, 24 (06) :519-523
[7]   Heat transfer analysis of ground heat exchangers with inclined boreholes [J].
Cui, P ;
Yang, HX ;
Fang, ZH .
APPLIED THERMAL ENGINEERING, 2006, 26 (11-12) :1169-1175
[8]   Subsoil heat exchangers for the air conditioning of livestock buildings [J].
Deglin, D ;
Van Caenegem, L ;
Dehon, P .
JOURNAL OF AGRICULTURAL ENGINEERING RESEARCH, 1999, 73 (02) :179-188
[9]   Cooled soil as a cooling source for buildings [J].
Givoni, Baruch .
SOLAR ENERGY, 2007, 81 (03) :316-328
[10]  
Hakan D., 2009, APPL THERM ENG, V29, P224