Global analysis of multi-compartment full-scale fire tests ('Rabot2012')

被引:11
作者
Beji, Tarek [1 ]
Verstockt, Steven [2 ]
Van de Walle, Rik [2 ]
Merci, Bart [1 ]
机构
[1] Ghent Univ UGent, Dept Flow Heat & Combust Mech, B-9000 Ghent, Belgium
[2] Ghent Univ iMinds, Multimedia Lab, Dept Elect & Informat Syst, B-9050 Ledeberg Ghent, Belgium
关键词
Enclosure fire; Multi-compartment; Full-scale fire tests; Fire modeling; Video monitoring;
D O I
10.1016/j.firesaf.2015.05.005
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A global analysis is presented of a series of four multi-compartment full-scale fire tests carried out in an apartment located in a high-rise building (called the 'Rabot' tower in the city of Ghent, Belgium) in 2012. The data set, available at http://multimedialab.elis.ugent.be/rabot2012/, is called 'Rabot2012'. These tests are believed to provide a valuable set of experimental data for fire modelling (CFD and two-zone) and monitoring purposes, for a number of reasons. First of all, the fuel package of intermediate complexity (i.e. two to three furniture items) and the ignition location were designed to focus on the initial flame spread and then the possible occurrence of secondary (and in one test tertiary) ignition. Also, very good repeatability is illustrated during the first minutes of the tests. Regarding the sensing aspect, in addition to the conventional tools such as thermocouples and velocity probes, a Video Fire Analysis (VFA) has been performed by applying smoke and flame detection algorithms to the footages obtained from a multi-view video network. Moreover, laboratory tests have been performed, putting the fuel packages as applied in the full-scale tests under a hood in free-burning conditions. The repeatability during the first minutes is confirmed and subsequent differences in fire development (free burning versus compartment set-up) are explained. This presentation of the 'Rabot2012' fire tests comprises: (1) a detailed description of the experimental set-up (i.e. geometry, fuel package and instrumentation), (2) an overview of the fire scenarios obtained in each of the four tests, and (3) a detailed account of the data processing carried out. Finally, elements of exploitation of the collected set of data are discussed. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:9 / 18
页数:10
相关论文
共 15 条
  • [1] Characterisation of Dalmarnock fire Test One
    Abecassis-Empis, C.
    Reszka, P.
    Steinhaus, T.
    Cowlard, A.
    Biteau, H.
    Welch, S.
    Rein, G.
    Torero, J. L.
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2008, 32 (07) : 1334 - 1343
  • [2] Beji T., 2012, FIRE TECHNOL
  • [3] Sensor Assisted Fire Fighting
    Cowlard, Adam
    Jahn, Wolfram
    Abecassis-Empis, Cecilia
    Rein, Guillermo
    Torero, Jose L.
    [J]. FIRE TECHNOLOGY, 2010, 46 (03) : 719 - 741
  • [4] Cox G., 1995, Combustion Fundamental of Fire, P329
  • [5] Determination of interface height from measured parameter profile in enclosure fire experiment
    He, YP
    Fernando, A
    Luo, MC
    [J]. FIRE SAFETY JOURNAL, 1998, 31 (01) : 19 - 38
  • [6] Forecasting fire growth using an inverse zone modelling approach
    Jahn, W.
    Rein, G.
    Torero, J. L.
    [J]. FIRE SAFETY JOURNAL, 2011, 46 (03) : 81 - 88
  • [7] JONES WW, 1984, COMBUST SCI TECHNOL, V35, P239
  • [8] MOMENTUM IMPLICATIONS FOR BUOYANT DIFFUSION FLAMES
    MCCAFFREY, BJ
    [J]. COMBUSTION AND FLAME, 1983, 52 (02) : 149 - 167
  • [9] Merci B., 2015, 11 IAFSS S CHRISTCH
  • [10] Characterizing Heat Release Rates Using an Inverse Fire Modeling Technique
    Overholt, Kristopher J.
    Ezekoye, Ofodike A.
    [J]. FIRE TECHNOLOGY, 2012, 48 (04) : 893 - 909