The frequency closed-loop control strategy of islanded power systems

被引:12
作者
Lin, Xiangning [1 ]
Weng, Hanli [1 ]
Zou, Qing [1 ]
Liu, Pei [1 ]
机构
[1] Huazhong Univ Sci & Technol, Elect Power Secur & High Efficiency Lab, Hubei Wuhanl 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
emergency pick-up step; fine-adjusting step; proportional-integral-differential (PID) closed-loop control; rough-adjusting step; under-frequency loading shedding (UFLS);
D O I
10.1109/TPWRS.2008.920044
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A novel power system frequency control strategy is designed in this paper, which is mainly used to improve the stability of the islanding power system. Detecting the change of circuit breaker status, it is feasible to identify the serious accidents, for instance, a generator outage or disconnection from main grids, and so on. The balanceable power before disturbance and the capacity of the removed power can be used to calculate the power deficiency. Then, appropriate load can be shed adaptively. In the subsequent regulating process, adapting to the various stages of frequency variation, the concepts of rough-adjusting step and fine-adjusting step are proposed to obtain a balance between shedding loads quickly and refining the load shed in every step. The concept of proportional-integral-differential (PID) is introduced to design a closed-loop control strategy to trace frequency variation, with which a balance between restraining the sharp drop of frequency effectively and releasing the reserved system capacity thoroughly can be obtained. Moreover, the frequency recovery curve can be optimized and the dead zone of control during the frequency rising stage can be avoided. Compared with the conventional under-frequency loading shedding (UFLS) schemes, the effectiveness of the control strategy presented has been verified by EMTDC simulation tests.
引用
收藏
页码:796 / 803
页数:8
相关论文
共 14 条
[1]   Optimal sectionalizing switches allocation in distribution networks [J].
Celli, G ;
Pilo, F .
IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (03) :1167-1172
[2]  
CHARLES C, 1995, IEEE T POWER SYST, V10, P1467
[3]   Protective relay setting of the tie line tripping and load shedding for the industrial power system [J].
Chen, CS ;
Ke, YL ;
Hsu, CT .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2000, 36 (05) :1226-1234
[4]   An adaptive approach to load shedding and spinning reserve control during underfrequency conditions [J].
Chuvychin, VN ;
Gurov, NS ;
Venkata, SS ;
Brown, RE .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (04) :1805-1810
[5]  
Ding ZP, 2006, PROCEEDINGS OF THE 2006 IEEE/SMC INTERNATIONAL CONFERENCE ON SYSTEM OF SYSTEMS ENGINEERING, P167
[6]   An automatic load shedding scheme including pumped-storage units [J].
Huang, SJ ;
Huang, CC .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2000, 15 (04) :427-432
[7]  
KUI KW, 2001, POWER SYST TECHNOL, V25, P31
[8]  
LIANG C, 2001, AUTOM ELECT POWER SY, V18, P53
[9]   Identification and validation of dynamic global load model parameters for use in power system frequency simulations [J].
OSullivan, JW ;
OMalley, MJ .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (02) :851-857
[10]   Islanding and load shedding schemes for captive power plants [J].
Rajamani, K ;
Hambarde, UK .
IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (03) :805-809