Fault Diagnosis and Condition Division Criterion of DC Gas Insulating Equipment Based on SF6 Partial Discharge Decomposition Characteristics

被引:20
|
作者
Zeng, Fuping [1 ]
Wu, Siying [1 ]
Yang, Xu [1 ,2 ]
Wan, Zhaofeng [1 ]
Tang, Ju [1 ]
Zhang, Mingxuan [1 ]
Yao, Qiang [3 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Hubei, Peoples R China
[2] Wuhan NARI Ltd Co, State Grid Elect Power Res Inst, Wuhan 430074, Hubei, Peoples R China
[3] Chongqing Power Co, Chongqing Elect Power Res Inst, Chongqing 401123, Peoples R China
基金
国家重点研发计划; 中国国家自然科学基金;
关键词
Negative DC; SF6 decomposition characteristics; minimum-redundancy-maximum-relevance; fault diagnosis; decision tree; condition evaluation; MUTUAL INFORMATION; FEATURE-EXTRACTION; RECOGNITION; SELECTION; CORONA; COMPONENTS; TRANSFORM;
D O I
10.1109/ACCESS.2019.2902413
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
SF6 decomposition characteristics directly reflect the generation, development, and evolution of internal faults in gas-insulated equipment (GIE). However, establishing the DC-GIE internal insulation condition comprehensive division criterion and fault diagnosis method based on SF6 decomposition characteristics remains unsolved. Therefore, partial discharge (PD) and SF6 decomposition characteristics of typical insulation defects from initial discharge to the breakdown process are discussed in this paper. The average discharge magnitude in a second Q(sec) is selected as an electrical feature to characterize the PD condition, and the PD state is divided into three levels, namely, mild PD, medium PD, and severe PD. SF6 decomposition experiments are conducted under different PD conditions of each defect, and the SF6 decomposition characteristics under different failure conditions are obtained. On this basis, we construct five feature sets of 36 characteristic quantities for GIE PD fault diagnosis and analyze the validity. A minimum-redundancy-maximum-relevance-based feature selection algorithm is used to optimize the characteristic quantities, and an optimal feature set is selected, i.e., {C(SO2)/C(T), C(SOF2)/C(CT), C(SO2F2)/C(ST)}. The characteristic quantities of SF6 decomposition component, which characterizes PD condition, are reconstructed, and the component characteristic criterion of PD condition division is proposed. Thus, a decision tree evaluation model for the PD condition of the typical insulation defect inside DC-GIE is constructed. This paper lays a foundation for the insulation condition evaluation and fault diagnosis of DC-GIE.
引用
收藏
页码:29869 / 29881
页数:13
相关论文
共 50 条
  • [21] Decomposition Characteristics of SF6 and Partial Discharge Recognition for Inflatable DC Wall Bushing Under Negative DC Conditions
    Zhu N.
    Zhang M.
    Xu X.
    Tang J.
    Zeng F.
    Zeng, Fuping (Fuping.zeng@whu.edu.cn), 1600, Science Press (46): : 947 - 956
  • [22] Deterioration characteristics of insulation subjected to partial discharge in SF6 gas
    Okabe, S
    Kawashima, T
    IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXHIBITION 2002: ASIA PACIFIC, VOLS 1-3, CONFERENCE PROCEEDINGS: NEW WAVE OF T&D TECHNOLOGY FROM ASIA PACIFIC, 2002, : 792 - 797
  • [23] Detection of Partial Discharge in SF6 Decomposition Gas Based on Modified Carbon Nanotubes Sensors
    Zhang, Xiaoxing
    Yang, Bing
    Liu, Wangting
    Zhang, Jinbin
    2012 INTERNATIONAL WORKSHOP ON INFORMATION AND ELECTRONICS ENGINEERING, 2012, 29 : 4107 - 4111
  • [24] Triangle Fault Diagnosis Method for SF6 Gas-Insulated Equipment
    Wu, Siying
    Zeng, Fuping
    Tang, Ju
    Yao, Qiang
    Miao, Yulong
    IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (04) : 1470 - 1477
  • [25] Study on the influence of adsorbent on SF6 decomposition characteristics under partial discharge
    Tang, J. (cqtangju@vip.sina.com), 1600, Chinese Society for Electrical Engineering (34):
  • [26] Study on Fault Decomposition Properties and Fault Diagnostic Criterion of Fluorocarbon Gas-a Substitute Gas for SF6
    Li K.
    Guo R.
    Zhang G.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 (12): : 2649 - 2656
  • [27] Partial Discharge Characteristics of the Surface Discharge in SF6/N2 of the Mixed Gas Under DC Voltage
    Hou Z.
    Guo R.
    Li J.
    Li, Junhao (junhaoli@mail.xjtu.edu.cn), 1600, Chinese Machine Press (35): : 3087 - 3096
  • [28] SF6 DECOMPOSITION IN GAS-INSULATED EQUIPMENT
    CHU, FY
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1986, 21 (05): : 693 - 725
  • [29] Influence of discharge quantity on SF6 decomposition under needle-plate dc partial discharge
    Liu, Min
    Tang, Ju
    Yao, Qiang
    Miao, Yulong
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [30] Partial Discharge Recognition through an Analysis of SF6 Decomposition Products Part 1: Decomposition Characteristics of SF6 under Four Different Partial Discharges
    Tang, Ju
    Liu, Fan
    Zhang, Xiaoxing
    Meng, Qinghong
    Zhou, Jiabin
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (01) : 29 - 36