Fault Diagnosis and Condition Division Criterion of DC Gas Insulating Equipment Based on SF6 Partial Discharge Decomposition Characteristics

被引:20
|
作者
Zeng, Fuping [1 ]
Wu, Siying [1 ]
Yang, Xu [1 ,2 ]
Wan, Zhaofeng [1 ]
Tang, Ju [1 ]
Zhang, Mingxuan [1 ]
Yao, Qiang [3 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Hubei, Peoples R China
[2] Wuhan NARI Ltd Co, State Grid Elect Power Res Inst, Wuhan 430074, Hubei, Peoples R China
[3] Chongqing Power Co, Chongqing Elect Power Res Inst, Chongqing 401123, Peoples R China
基金
国家重点研发计划; 中国国家自然科学基金;
关键词
Negative DC; SF6 decomposition characteristics; minimum-redundancy-maximum-relevance; fault diagnosis; decision tree; condition evaluation; MUTUAL INFORMATION; FEATURE-EXTRACTION; RECOGNITION; SELECTION; CORONA; COMPONENTS; TRANSFORM;
D O I
10.1109/ACCESS.2019.2902413
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
SF6 decomposition characteristics directly reflect the generation, development, and evolution of internal faults in gas-insulated equipment (GIE). However, establishing the DC-GIE internal insulation condition comprehensive division criterion and fault diagnosis method based on SF6 decomposition characteristics remains unsolved. Therefore, partial discharge (PD) and SF6 decomposition characteristics of typical insulation defects from initial discharge to the breakdown process are discussed in this paper. The average discharge magnitude in a second Q(sec) is selected as an electrical feature to characterize the PD condition, and the PD state is divided into three levels, namely, mild PD, medium PD, and severe PD. SF6 decomposition experiments are conducted under different PD conditions of each defect, and the SF6 decomposition characteristics under different failure conditions are obtained. On this basis, we construct five feature sets of 36 characteristic quantities for GIE PD fault diagnosis and analyze the validity. A minimum-redundancy-maximum-relevance-based feature selection algorithm is used to optimize the characteristic quantities, and an optimal feature set is selected, i.e., {C(SO2)/C(T), C(SOF2)/C(CT), C(SO2F2)/C(ST)}. The characteristic quantities of SF6 decomposition component, which characterizes PD condition, are reconstructed, and the component characteristic criterion of PD condition division is proposed. Thus, a decision tree evaluation model for the PD condition of the typical insulation defect inside DC-GIE is constructed. This paper lays a foundation for the insulation condition evaluation and fault diagnosis of DC-GIE.
引用
收藏
页码:29869 / 29881
页数:13
相关论文
共 50 条
  • [1] Evaluating DC Partial Discharge With SF6 Decomposition Characteristics
    Zeng, Fuping
    Lei, Zhicheng
    Yang, Xu
    Tang, Ju
    Yao, Qiang
    Miao, Yulong
    IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (04) : 1383 - 1392
  • [2] Defect Diagnosis of HVDC Bushings Based on SF6 Decomposition and Partial Discharge Characteristics
    Chen, Ming
    Liu, Xuandong
    Ma, Jingtan
    Zhang, Lingli
    Wen, Tao
    Zhu, Zhihao
    2017 1ST INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE), 2017, : 675 - 679
  • [3] SF6 Partial Overthermal Decomposition Characteristics of Thermal Fault in Organic Insulating Materials
    Zeng, Fuping
    Tang, Ju
    Zhang, Xiaoxing
    Yao, Qiang
    Miao, Yulong
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (02) : 829 - 837
  • [4] Partial Discharge Characteristics of Surface Discharge in SF6 Gas Under DC Voltage
    Hou Z.
    Sun S.
    Guo R.
    Pang P.
    Li J.
    Li, Junhao (junhaoli@mail.xjtu.edu.cn), 1649, Science Press (46): : 1649 - 1657
  • [5] Correlation characteristics between gas pressure and SF6 decomposition under negative DC partial discharge
    Tang, Ju
    Yang, Dong
    Zeng, Fuping
    Tang, Bowen
    Li, Ke
    Yao, Qiang
    Miao, Yulong
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (05) : 1240 - 1246
  • [6] Fault State Assessment for Partial Discharge Based on SF6 Decomposition Characteristic Under Negative DC
    Yang X.
    Zhang J.
    Zhang J.
    Cheng L.
    Zhang X.
    Nie D.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (12): : 3794 - 3803
  • [7] Influence of Atmospheric Pressure on the Decomposition Characteristics of SF6 Under Partial Discharge at Negative Polarity DC Condition
    Tang J.
    Li K.
    Yao Q.
    Miao Y.
    Zeng F.
    Zhang C.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (01): : 159 - 166
  • [8] Comparison of Partial Discharge Characteristics in SF6 Gas Under AC and DC
    Jo, Hyang-Eun
    Wang, Guoming
    Kim, Sun-Jae
    Kil, Gyung-Suk
    TRANSACTIONS ON ELECTRICAL AND ELECTRONIC MATERIALS, 2015, 16 (06) : 323 - 327
  • [9] Partial Discharge Failure Evaluation Based on SF6 Decomposition Characteristics
    Zhu N.
    Wu S.
    Zeng F.
    Tang J.
    Lei Z.
    Xu X.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2019, 39 (03): : 933 - 942
  • [10] GIS Fault Diagnosis Method Based on The Identification of SF6 Gas Decomposition Product Fault Characteristics
    Zhang, Ruien
    Li, Xinran
    Fu, Chuanfu
    Liu, Xueyang
    Wang, Chunmin
    Fan, Xiaozhou
    Zhang, Wenqi
    PROCEEDINGS OF 2022 12TH INTERNATIONAL CONFERENCE ON POWER, ENERGY AND ELECTRICAL ENGINEERING (CPEEE 2022), 2022, : 149 - 153