Air infiltration rates in the bedrooms of 202 residences and estimated parametric infiltration rate distribution in Guangzhou, China

被引:45
作者
Cheng, Pok Lun [1 ]
Li, Xiaofeng [1 ,2 ]
机构
[1] Tsinghua Univ, Sch Architecture, Dept Bldg Sci, Beijing 100084, Peoples R China
[2] Tsinghua Univ, Beijing Key Lab Indoor Air Qual Evaluat & Control, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
Air change rate; Air infiltration rate; Carbon dioxide; Indoor air quality; Bedroom; China; EXCHANGE-RATES; VENTILATION; BUILDINGS; INDOOR;
D O I
10.1016/j.enbuild.2017.12.062
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study investigates the overnight air infiltration rates of 202 natural ventilated bedrooms, measured in August to September 2016 (cooling season) in Guangzhou, China. The rates were calculated and analyzed based on a single zone mass balance equation, using CO2 produced by the sleeping occupants as tracer gas source. It was found that additional ventilation is required to satisfy the Chinese building code, where only 16% had the minimum required amount of ventilation. The air infiltration rates fit a log-normal distribution (R-2 = 0.85) ranging from 0.05 to 1.32 h(-1), with an arithmetic mean of 0.41 h(-1). None of these parameters had an effect on the air infiltration rate distribution: Absolute indoor and outdoor temperature difference, window age, building type (two different window standards), floor level of bedroom and openable window area. The provided data can be used in analyzing cooling energy and indoor air quality from outdoor pollution in natural ventilated residential buildings in south China. (C) 2018 Elsevier B.V. All rights reserved.
引用
收藏
页码:219 / 225
页数:7
相关论文
共 41 条
[1]   Ventilation of air-conditioned residential buildings: A case study in Hong Kong [J].
Ai, Z. T. ;
Mak, C. M. ;
Cui, D. J. ;
Xue, P. .
ENERGY AND BUILDINGS, 2016, 127 :116-127
[2]  
[Anonymous], 2013, 6212013 ASHRAE
[3]  
[Anonymous], 2012, JGJ75
[4]  
ASHRAE, 2013, FUND HDB THERM COMFF
[5]  
Beijing City Lab, URB DYN CHIN
[6]   Ventilation rates in the bedrooms of 500 Danish children [J].
Beko, Gabriel ;
Lund, Toste ;
Nors, Fredrik ;
Toftum, Jorn ;
Clausen, Geo .
BUILDING AND ENVIRONMENT, 2010, 45 (10) :2289-2295
[7]   Association between ventilation rates in 390 Swedish homes and allergic symptoms in children [J].
Bornehag, CG ;
Sundell, J ;
Hägerhed-Engman, L ;
Sigsgaard, T .
INDOOR AIR, 2005, 15 (04) :275-280
[8]   MODELING AND MONITORING OF CO, NO AND NO2 IN A MODERN TOWNHOUSE [J].
BORRAZZO, JE ;
OSBORN, JF ;
FORTMANN, RC ;
KEEFER, RL ;
DAVIDSON, CI .
ATMOSPHERIC ENVIRONMENT, 1987, 21 (02) :299-311
[9]   A review of air exchange rate models for air pollution exposure assessments [J].
Breen, Michael S. ;
Schultz, Bradley D. ;
Sohn, Michael D. ;
Long, Thomas ;
Langstaff, John ;
Williams, Ronald ;
Isaacs, Kristin ;
Meng, Qing Yu ;
Stallings, Casson ;
Smith, Luther .
JOURNAL OF EXPOSURE SCIENCE AND ENVIRONMENTAL EPIDEMIOLOGY, 2014, 24 (06) :555-563
[10]   Air infiltration assessment for industrial buildings [J].
Brinks, Pascal ;
Kornadt, Oliver ;
Oly, Rene .
ENERGY AND BUILDINGS, 2015, 86 :663-676