The Fault Detection, Localization, and Tolerant Operation of Modular Multilevel Converters with an Insulated Gate Bipolar Transistor (IGBT) Open Circuit Fault

被引:10
作者
Li, Wei [1 ]
Li, Gengyin [1 ]
Zeng, Rong [2 ]
Ni, Kai [3 ]
Hu, Yihua [3 ]
Wen, Huiqing [4 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
[2] Oak Ridge Natl Lab, Power Elect & Elect Machine Grp, Knoxville, TN 37932 USA
[3] Univ Liverpool, Dept Elect Engn & Elect, Liverpool L69 3GJ, Merseyside, England
[4] Xian Jiaotong Liverpool Univ, Dept Elect & Elect Engn, Suzhou 215123, Peoples R China
关键词
modular multi-level converter; fault detection; circulating current; output current observation; fault localization; fault-tolerant operation; UNBALANCED GRID CONDITIONS; HVDC SYSTEM; OBSERVER; DESIGN;
D O I
10.3390/en11040837
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Reliability is one of the critical issues for a modular multilevel converter (MMC) since it consists of a large number of series-connected power electronics submodules (SMs). In this paper, a complete control strategy including fault detection, localization, and tolerant operation is proposed for the MMC under an insulated gate bipolar transistor (IGBT) open circuit fault. According to the output characteristics of the SM with the open-circuit fault of IGBT, a fault detection method based on the circulating current and output current observation is used. In order to further precisely locate the position of the faulty SM, a fault localization method based on the SM capacitor voltage observation is developed. After the faulty SM is isolated, the continuous operation of the converter is ensured by adopting the fault-tolerant strategy based on the use of redundant modules. To verify the proposed fault detection, fault localization, and fault-tolerant operation strategies, a 900 kVA MMC system under the conditions of an IGBT open circuit is developed in the Matlab/Simulink platform. The capabilities of rapid detection, precise positioning, and fault-tolerant operation of the investigated detection and control algorithms are also demonstrated.
引用
收藏
页数:20
相关论文
共 32 条
[1]  
[Anonymous], 2013, 2013 15 EUR C POWER, DOI DOI 10.1109/EPE.2013.6634401
[2]  
[Anonymous], 2003, PROC IEEE BOLOGNA PO
[3]   Fault-Tolerant Approach for Modular Multilevel Converters Under Submodule Faults [J].
Deng, Fujin ;
Tian, Yanjun ;
Zhu, Rongwu ;
Chen, Zhe .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2016, 63 (11) :7253-7263
[4]   Fault Detection and Localization Method for Modular Multilevel Converters [J].
Deng, Fujin ;
Chen, Zhe ;
Khan, Mohammad Rezwan ;
Zhu, Rongwu .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2015, 30 (05) :2721-2732
[5]   Modeling and Control of a Modular Multilevel Converter-Based HVDC System Under Unbalanced Grid Conditions [J].
Guan, Minyuan ;
Xu, Zheng .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2012, 27 (12) :4858-4867
[6]   Fast fault detection method for modular multilevel converter semiconductor power switches [J].
Haghnazari, Saeed ;
Khodabandeh, Masih ;
Zolghadri, Mohammad Reza .
IET POWER ELECTRONICS, 2016, 9 (02) :165-174
[7]   Dynamic Analysis of Modular Multilevel Converters [J].
Harnefors, Lennart ;
Antonopoulos, Antonios ;
Norrga, Staffan ;
Angquist, Lennart ;
Nee, Hans-Peter .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (07) :2526-2537
[8]   Energy-balancing Control Strategy for Modular Multilevel Converters Under Submodule Fault Conditions [J].
Hu, Pengfei ;
Jiang, Daozhuo ;
Zhou, Yuebin ;
Liang, Yiqiao ;
Guo, Jie ;
Lin, Zhiyong .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (09) :5021-5030
[9]  
HU X, 2016, P IEEE PIMRC VAL SPA, P1, DOI DOI 10.1109/EITT.2016.8
[10]   Steady-State Analysis of Interaction Between Harmonic Components of Arm and Line Quantities of Modular Multilevel Converters [J].
Ilves, Kalle ;
Antonopoulos, Antonios ;
Norrga, Staffan ;
Nee, Hans-Peter .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2012, 27 (01) :57-68