Study on ammonia/water hybrid absorption/compression heat pump cycle to produce high temperature process water

被引:27
作者
Jung, Chung Woo [1 ]
Song, Joo Young [1 ]
Kang, Yong Tae [1 ]
机构
[1] Korea Univ, Sch Mech Engn, 145 Anam Ro, Seoul 02841, South Korea
关键词
Absorber heat transfer rate; Ammonia-water absorption; Hybrid compression/absorption cycle; High temperature process water; WASTE HEAT; REFRIGERANT; MIXTURES; SYSTEMS; OZONE; VAPOR; R134A;
D O I
10.1016/j.energy.2017.12.141
中图分类号
O414.1 [热力学];
学科分类号
摘要
The objectives of this paper are to analyze the heat transfer characteristics during the ammonia water absorption process for the hybrid absorption/compression heat pump system application. The hybrid absorption/compression heat pump cycle aims at obtaining the high temperature process water. The parametric analysis on the effects of each key parameter, which are system high-pressure, ammonia weak solution concentration, ammonia weak solution and vapor flow rates is carried out. It is found that the increases in the high pressure and ammonia weak solution flow rate have positive effects on the absorber heat transfer rate, whereas the increase in the weak solution concentration does negative effect. It is also found that the weak solution concentration acts as the most important parameter to obtain the high temperature process water. As the weak solution concentration increases, the absorber heat transfer rate decreases, but the system COP tends to increase. It is concluded that the concentration of the weak solution should be maintained at approximately 0.40-0.45, the flow rate of the weak solution be lower than 0.03 kg/s, and the high-pressure be higher than 1700 kPa to obtain process water of higher than 80 degrees C. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:458 / 467
页数:10
相关论文
共 40 条
[1]   Cooling, heating, generating power, and recovering waste heat with thermoelectric systems [J].
Bell, Lon E. .
SCIENCE, 2008, 321 (5895) :1457-1461
[2]  
Boahen S, 2017, INT J AIR-COND REFRI, V25, DOI 10.1142/S2010132517500249
[3]  
Bolaji BO, 2011, COMP ANAL PERFORMANC
[4]   Comparison of the working domains of some compression heat pumps and a compression-absorption heat pump [J].
Brunin, O ;
Feidt, M ;
Hivet, B .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1997, 20 (05) :308-318
[5]   ALTERNATIVE REFRIGERANTS R123A, R134, R141B, R142B, AND R152A - CRITICAL-TEMPERATURE, REFRACTIVE-INDEX, SURFACE-TENSION, AND ESTIMATES OF LIQUID, VAPOR, AND CRITICAL DENSITIES [J].
CHAE, HB ;
SCHMIDT, JW ;
MOLDOVER, MR .
JOURNAL OF PHYSICAL CHEMISTRY, 1990, 94 (25) :8840-8845
[6]   THINNING OF THE OZONE-LAYER - FACTS AND CONSEQUENCES [J].
COLDIRON, BM .
JOURNAL OF THE AMERICAN ACADEMY OF DERMATOLOGY, 1992, 27 (05) :653-662
[7]  
Dieckmann J., 1999, Global Comparative Analysis of HFC and Alternative Technologies for Refrigeration, Air Conditioning, Foam, Solvent, Aerosol Propellant, and Fire Protection Applications
[8]  
Formigoni C, 1998, CH4 ENERGIA METANO, V15, P7
[9]  
Garrabrant M., 2013, ASME INT C EN SUST M
[10]  
Garrabrant MA, 2014, INT SORPT HEAT PUMP