Corrosion of galvanized pipes in the hot water supply system

被引:2
作者
Andrianov, Alexey [1 ]
Spitsov, Dmitry [1 ]
机构
[1] Moscow State Univ Civil Engn, Yaroslavskoye Shosse 26, Moscow 129337, Russia
来源
INTERNATIONAL SCIENCE CONFERENCE SPBWOSCE-2016 - SMART CITY | 2017年 / 106卷
关键词
CAST-IRON; RELEASE; BIOCORROSION; SURFACE; STEEL;
D O I
10.1051/matecconf/201710603028
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The paper describes the problem of steel pipes corrosion in domestic hot water supply systems. A case study of abnormally high rate of corrosion of galvanized steel pipes in a hot water supply system, installed in a complex of residential and public buildings, was considered. The rapid corrosion led to premature failure of these pipelines. Onsite visual inspection, chemical analysis of the tap water with LSI/RSI calculation and scanning electron microscopy and energy-dispersive X-ray spectroscopy analysis were used during this study. The basic factors that lead to pitting corrosion were established: quality of source water (its high corrosion activity), high temperature and local increase in oxygen content near the pipe surface. A possibility of microbial corrosion was also assumed.
引用
收藏
页数:7
相关论文
共 21 条
[1]  
Chukhin V., 2014, INT C EXH, V1
[2]   Biofouling and biocorrosion in industrial water systems [J].
Coetser, SE ;
Cloete, TE .
CRITICAL REVIEWS IN MICROBIOLOGY, 2005, 31 (04) :213-232
[3]   Corrosion behaviour and biocorrosion of galvanized steel water distribution systems [J].
Delaunois, F. ;
Tosar, F. ;
Vitry, V. .
BIOELECTROCHEMISTRY, 2014, 97 :110-119
[4]   Corrosion failure analysis of galvanized steel pipes in a water irrigation system [J].
Della Rovere, C. A. ;
Silva, R. ;
Moretti, C. ;
Kuri, S. E. .
ENGINEERING FAILURE ANALYSIS, 2013, 33 :381-386
[5]   Changes of the corrosion potential of iron in stagnation and flow conditions and their relationship with metal release [J].
Fabbricino, Massimiliano ;
Korshin, Gregory V. .
WATER RESEARCH, 2014, 62 :136-146
[6]  
FORD T, 1990, ADV MICROB ECOL, V11, P231
[7]   Physiochemical characterization of five iron tubercles from a single drinking water distribution system: Possible new insights on their formation and growth [J].
Gerke, Tammie L. ;
Maynard, J. Barry ;
Schock, Michael R. ;
Lytle, Darren L. .
CORROSION SCIENCE, 2008, 50 (07) :2030-2039
[8]   Asset deterioration and discolouration in water distribution systems [J].
Husband, P. S. ;
Boxall, J. B. .
WATER RESEARCH, 2011, 45 (01) :113-124
[9]   ROLE OF SULFATE-REDUCING BACTERIA IN CORROSION OF MILD-STEEL - A REVIEW [J].
LEE, W ;
LEWANDOWSKI, Z ;
NIELSEN, PH ;
HAMILTON, WA .
BIOFOULING, 1995, 8 (03) :165-+
[10]   Impact of flow rate on corrosion of cast iron and quality of re-mineralized seawater reverse osmosis (SWRO) membrane product water [J].
Liang, Juan ;
Deng, Anqi ;
Xie, Rongjing ;
Gomez, Mylene ;
Hu, Jiangyong ;
Zhang, Jufang ;
Ong, Choon Nam ;
Adin, Avner .
DESALINATION, 2013, 322 :76-83