A Novel Solid-State Circuit Breaker With Self-Adapt Fault Current Limiting Capability for LVDC Distribution Network

被引:102
作者
Li, Bin [1 ]
He, Jiawei [1 ]
Li, Ye [1 ]
Li, Ruisheng [2 ]
机构
[1] Tianjin Univ, Key Lab Smart Grid, Minist Educ, Tianjin 300072, Peoples R China
[2] XJ Grp Corp, Xuchang 461000, Peoples R China
基金
中国国家自然科学基金;
关键词
DC fault ride-through; fault current limitation; low-voltage dc (LVDC) distribution network; solid-state circuit breaker (SSCB); PROTECTION; CONVERTER;
D O I
10.1109/TPEL.2018.2850441
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
DC fault current limitation is important for the low-voltage dc distribution network, because the existing dc selective protection cannot act fast enough. However, the typical dc fault current limiting method-installing dc reactors directly in the dc system-will lead to negative influence on the system normal operation and dc circuit breaker (DCCB) fast isolation. This paper proposed a novel solid-state circuit breaker (SSCB) with self-adapt fault current limiting capability, namely, no negative influence on the dc distribution network normal operation, swift fault current limiting response to the dc fault, and efficient cooperation between the fault current limitation and isolation. The hybrid configuration strategy of the proposed SSCB and mechanical DCCB for multi-terminal dc distribution network is proposed to reduce the conducting power loss and investment from the scale of the whole system. Finally, the experiment tests and simulation cases are carried out to verify the working principle and superiorities of the proposed SSCB.
引用
收藏
页码:3516 / 3529
页数:14
相关论文
共 20 条
[11]  
Kong W. Y., 2012, DSTOTN1074
[12]  
Lei Feng, 2016, 2016 IEEE 8th International Power Electronics and Motion Control Conference (IPEMC-ECCE Asia), P2371, DOI 10.1109/IPEMC.2016.7512668
[13]   Studies on the Application of R-SFCL in the VSC-Based DC Distribution System [J].
Li, Bin ;
He, Jiawei .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2016, 26 (03)
[14]   Continuous Operation of Radial Multiterminal HVDC Systems Under DC Fault [J].
Li, Rui ;
Xu, Lie ;
Holliday, Derrick ;
Page, Frederick ;
Finney, Stephen J. ;
Williams, Barry W. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2016, 31 (01) :351-361
[15]   Solid-State Circuit Breaker Snubber Design for Transient Overvoltage Suppression at Bus Fault Interruption in Low-Voltage DC Microgrid [J].
Liu, Fei ;
Liu, Wenjun ;
Zha, Xiaoming ;
Yang, Hua ;
Feng, Kun .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2017, 32 (04) :3007-3021
[16]   A Hybrid Current-Limiting Circuit for DC Line Fault in Multiterminal VSC-HVDC System [J].
Liu, Jian ;
Tai, Nengling ;
Fan, Chunju ;
Chen, Shi .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2017, 64 (07) :5595-5607
[17]   BOOST TYPE PWM HVDC TRANSMISSION-SYSTEM [J].
OOI, BT ;
WANG, X .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (04) :1557-1563
[18]   Protection of Low-Voltage DC Microgrids [J].
Salomonsson, Daniel ;
Soder, Lennart ;
Sannino, Ambra .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) :1045-1053
[19]   A Surgeless Solid-State DC Circuit Breaker for Voltage-Source-Converter-Based HVDC Systems [J].
Sano, Kenichiro ;
Takasaki, Masahiro .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2014, 50 (04) :2690-2699
[20]   Short-Circuit and Ground Fault Analyses and Location in VSC-Based DC Network Cables [J].
Yang, Jin ;
Fletcher, John E. ;
O'Reilly, John .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2012, 59 (10) :3827-3837