Frequency Response Analyses Via Rational Function Fitting

被引:0
|
作者
Youssouf, R. M. [1 ]
Meghnefi, F. [1 ]
Fofana, I. [1 ]
机构
[1] Univ Quebec Chicoutimi, Chicoutimi, PQ G7H 2B1, Canada
关键词
transformer; sweep frequency response analysis; poles; rational function; fitting;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Based on terminal measurements on a single phase, low voltage transformer model, it is demonstrated how faults introduced at different positions along the winding could be identified with reasonable accuracy using rational function fitting. Fault in the present context represents a discrete change, e. g. short-circuiting a few turns within a disc (i.e. pre dominantly an inductive change) and the transfer impedances are measured. The proposed method aims at fitting the measured data to iteratively the zeros/poles of the transfer function. Location of such synthesized zeros/poles reveals the nature of fault. Results presented demonstrate the feasibility of this method.