A Novel Low Voltage Ride Through Control Method for Current Source Grid-Connected Photovoltaic Inverters

被引:25
作者
Geng, Yiwen [1 ]
Yang, Ke [1 ]
Lai, Zou [1 ]
Zheng, Pengfei [1 ]
Liu, Haiwei [1 ]
Deng, Renxiong [1 ]
机构
[1] China Univ Min & Technol, Sch Elect & Power Engn, Xuzhou 221116, Jiangsu, Peoples R China
基金
中国国家自然科学基金;
关键词
Current source inverter (CSI); photovoltaic application; low voltage ride through (LVRT); grid voltage sag;
D O I
10.1109/ACCESS.2019.2911477
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Due to their inherent topology characteristic, current source grid-connected photovoltaic inverters cannot realize low voltage ride through (LVRT) during a serious sag in the grid voltage. Based on mathematical models of three-phase current source grid-connected photovoltaic (PV) inverters, this paper analyzes quantitatively the relationship between steady-state DC-link current and grid voltage, and also derives the steady-state working range of the DC-link current in CSIs. Based on the steady-state working range of the DC-link current and the native characteristics of PV cells, this paper indicates the fundamental reason that three-phase current source inverter cannot realize LVRT. To solve this problem, an improved topology of a current source grid-connected photovoltaic inverter is adopted in this paper, where a chopper circuit is added in the DC link. Meanwhile, a novel control strategy is further proposed to realize LVRT under balanced and unbalanced grid voltage conditions. Finally, the simulation and experiment results verify the effectiveness of the proposed method.
引用
收藏
页码:51735 / 51748
页数:14
相关论文
共 26 条
[1]   Transformer-Less Grid Feeding Current Source Inverter for Solar Photovoltaic System [J].
Anand, Sandeep ;
Gundlapalli, Saikrishna Kashyap ;
Fernandes, B. G. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2014, 61 (10) :5334-5344
[2]  
[Anonymous], 2011, 6172011 QGDW
[3]  
[鲍建宇 Bao Jianyu], 2016, [电工技术学报, Transactions of China Electrotechnical Society], V31, P70
[4]  
Chandesris L., 2016, GLOBAL COMMUNICATION, P1, DOI DOI 10.1109/PEDG.2016.7527027
[5]  
[陈浩 Chen Hao], 2013, [电网技术, Power System Technology], V37, P1464
[6]   Low-voltage ride-through of a full converter wind turbine with permanent magnet generator [J].
Conroy, J. F. ;
Watson, R. .
IET RENEWABLE POWER GENERATION, 2007, 1 (03) :182-189
[7]   Unified DC-Link Current Control for Low-Voltage Ride-Through in Current-Source-Converter-Based Wind Energy Conversion Systems [J].
Dai, Jingya ;
Xu, Dewei ;
Wu, Bin ;
Zargari, Navid R. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (01) :288-297
[8]  
Diaz-Franco F., 2016, 2016 North American Power Symposium (NAPS), P1
[9]   Adaptive DC-Link Voltage Control of Two-Stage Photovoltaic Inverter During Low Voltage Ride-Through Operation [J].
Ding, Guangqian ;
Gao, Feng ;
Tian, Hao ;
Ma, Cong ;
Chen, Mengxing ;
He, Guoqing ;
Liu, Yingliang .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2016, 31 (06) :4182-4194
[10]   LVRT Capability of DFIG-Based WECS Under Asymmetrical Grid Fault Condition [J].
Geng, Hua ;
Liu, Cong ;
Yang, Geng .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (06) :2495-2509