Ejector expansion refrigeration system: Ejector design and performance evaluation

被引:53
作者
Hassanain, M. [1 ]
Elgendy, E. [1 ]
Fatouh, M. [1 ]
机构
[1] Fac Engn El Mattaria, Dept Power Mech Engn, Cairo, Egypt
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2015年 / 58卷
关键词
Constant-area ejector; Ejector sizing; Two-phase flow ejector; Ejector expansion refrigeration system; Performance enhancement; VAPOR COMPRESSION REFRIGERATION; 2-PHASE EJECTOR; CYCLE; PUMP;
D O I
10.1016/j.ijrefrig.2015.05.018
中图分类号
O414.1 [热力学];
学科分类号
摘要
Use of a two-phase flow ejector as an expansion device in vapor compression refrigeration systems is one of the efficient ways to enhance its performance. The present work aims to design a constant-area two phase flow ejector and to evaluate performance characteristics of the ejector expansion refrigeration system working with R134a. In order to achieve these objectives, a simulation program is developed and effects of operating conditions and ejector internal efficiencies on the system performance are investigated using EES software. Comparison between present results and published experimental data revealed that the developed model can predict the system COP with a maximum error of 2.3%. The system COP increased by 87.5% as evaporation temperature changed from -10 degrees C to 10 degrees C. Finally, correlations to size ejector main diameters as a function of operating conditions, system cooling capacity and ejector internal efficiencies are reported. (C) 2015 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:1 / 13
页数:13
相关论文
共 28 条
[1]   A CFD-based investigation of the energy performance of two-phase R744 ejectors to recover the expansion work in refrigeration systems: An irreversibility analysis [J].
Banasiak, Krzysztof ;
Palacz, Michal ;
Hafner, Armin ;
Bulinski, Zbigniew ;
Smolka, Jacek ;
Nowak, Andrzej J. ;
Fic, Adam .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 40 :328-337
[2]   Performance improvement of the vapour compression refrigeration cycle by a two-phase constant area ejector [J].
Bilir, Nagihan ;
Ersoy, H. Kursad .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2009, 33 (05) :469-480
[3]   Experimental study on R-134a refrigeration system using a two-phase ejector as an expansion device [J].
Chaiwongsa, Praitoon ;
Wongwises, Somchai .
APPLIED THERMAL ENGINEERING, 2008, 28 (5-6) :467-477
[4]   Effect of throat diameters of the ejector on the performance of the refrigeration cycle using a two-phase ejector as an expansion device [J].
Chaiwongsa, Praitoon ;
Wongwises, Somchai .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (04) :601-608
[5]   Ejectors: applications in refrigeration technology [J].
Chunnanond, K ;
Aphornratana, S .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2004, 8 (02) :129-155
[6]   Particular characteristics of transcritical CO2 refrigeration cycle with an ejector [J].
Deng, Jian-qiang ;
Jiang, Pei-xue ;
Lu, Tao ;
Lu, Wei .
APPLIED THERMAL ENGINEERING, 2007, 27 (2-3) :381-388
[7]   Experimental investigation on the performance of the refrigeration cycle using a two-phase ejector as an expansion device [J].
Disawas, S ;
Wongwises, S .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (06) :587-594
[8]  
Egyptian electricity holding company, 2012, ANN REPORT
[9]   Experimental validation of a prototype ejector designed to reduce throttling losses encountered in transcritical R744 system operation [J].
Elbel, Stefan ;
Hrnjak, Pega .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (03) :411-422
[10]   Historical and present developments of ejector refrigeration systems with emphasis on transcritical carbon dioxide air-conditioning applications [J].
Elbel, Stefan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (07) :1545-1561