Ignition hazard evaluation on A2L refrigerants in situations of service and maintenance

被引:23
作者
Imamura, Tomohiko [1 ]
Kamiya, Kyoko [2 ]
Sugawa, Osami [1 ]
机构
[1] Tokyo Univ Sci, Dept Mech Engn, Chino, Nagano 3910292, Japan
[2] Japan Specialist Law Engn Corp, Kita Ku, Okayama 7000975, Japan
关键词
A2L refrigerants; Hazard evaluation; Jet flame; Ignition; Flame propagation;
D O I
10.1016/j.jlp.2014.12.018
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
To restrict the progress of the global warming, A2L refrigerants such as 2,3,3,3-tetrafluoroprop-1-ene (R1234yf), (Z/E)-1,3,3,3-tetrafluoroprop-1-ene (R1234ze), and difluoromethane (R32) have been expected of alternatives to the standard refrigerants currently in use. The ignition hazard of A2L refrigerants under plausible accident situations in service and maintenance was examined experimentally for two cases: leakage of an A2L refrigerant from a pinhole in a pipe or hose (Scenario 1), and leakage of an A2L refrigerant into an item of equipment used for service and maintenance, such as a collection device (Scenario 2). In Scenario 1, the location of the flammable zone and the possibility of a jet flame being formed instantaneously on contact with an ignition source were examined. Even when R1234yf leaked from a 4 mm 4) pinhole (corresponding to breakage of a pipe), the flammable zone extended only about 10 cm from the pinhole in the downstream region. In an ignition test with a continuous spark as the ignition source, a pale emission appeared only near the spark, and the flame did not propagate to the rest of the refrigerant jet. In Scenario 2, the accumulation and ignition behaviors of A2L refrigerants in a model collection device were examined experimentally. Ignition and flame propagation occurred in a test on a model collection device lacking slits, whereas when slits wider than 20 mm were present, ignition and flame propagation did not occur. Even if R1234yf leaked into the model collection device, provided that slits of an effective width were present, the R1234yf could diffuse through slits and barely accumulated, and no ignition or flame propagation occurred. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:555 / 563
页数:9
相关论文
共 6 条
[1]  
ASHRAE, 2013, 342013 ANSIASHRAE
[2]  
Imamura T., 2012, P INT S NEW REFR ENV, P65
[3]  
Imamura T., 2013, RISK ASSESSMENT MILD, P35
[4]  
Spatz M, 2008, SAE WORLD C DETR MIC
[5]   Burning velocity measurements of fluoropropanes by the spherical-vessel method [J].
Takizawa, Kenji ;
Takahashi, Akifumi ;
Tokuhashi, Kazuaki ;
Kondo, Shigeo ;
Sekiya, Akira .
JOURNAL OF FLUORINE CHEMISTRY, 2008, 129 (08) :713-719
[6]   Flammability assessment of CH2=CFCF3: Comparison with fluoroalkenes and fluoroalkanes [J].
Takizawa, Kenji ;
Tokuhashi, Kazuaki ;
Kondo, Shigeo .
JOURNAL OF HAZARDOUS MATERIALS, 2009, 172 (2-3) :1329-1338