Generator Reactive Power Constrained Voltage Stability Analysis of Large Power System Under Critical Line Outage

被引:0
作者
Naik, S. D. [1 ]
机构
[1] Shri Ramdeobaba Coll Engn & Management, Dept Elect Engn, Nagpur, Maharashtra, India
来源
2020 8TH INTERNATIONAL ELECTRICAL ENGINEERING CONGRESS (IEECON) | 2020年
关键词
Voltage stability; Loadability; Reactive power; Automatic Voltage Regulator (AVR); Overexcited Limiter (OEL);
D O I
10.1109/iEECON48109.2020.229458
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Heavy loads and large disturbances are usually manifested into voltage instability of power systems. The increased transaction levels in open access power systems are main cause of stressful operation of the system. Several countries around the globe have reported incidences of voltage instability in recent years. It has become a top priority of power engineers to solve voltage instability related problems and control the voltage profile. Action of Automatic Voltage Regulators (AVRs) of the generators is the first line of defense against voltage instability. The challenge of maintaining power system voltage stability and security under outage conditions is well taken by the power system engineers. The security assessment in the event of a contingency provides the knowledge about the current and future system state. When generator reactive power is automatically regulated, the voltage stability is improved. In present studies IEEE 6 Bus Power system is considered for static voltage stability. The co-relationship of upper limits of generator reactive power with voltage stability and maximum system loadability under critical line outage is established.
引用
收藏
页数:4
相关论文
共 15 条
[1]   THE CONTINUATION POWER FLOW - A TOOL FOR STEADY-STATE VOLTAGE STABILITY ANALYSIS [J].
AJJARAPU, V ;
CHRISTY, C .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (01) :416-423
[2]   Calculation of weighting factors of static security indices used in contingency ranking of power systems based on fuzzy logic and analytical hierarchy process [J].
Baghaee, H. R. ;
Abedi, M. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2011, 33 (04) :855-860
[3]   Decentralized secondary voltage control using voltage drop compensator among power plants [J].
da Silva, Rui Jovita G. C. ;
Zambroni de Souza, A. C. ;
Leme, Rafael C. ;
Sonoda, Dabit .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 47 :61-68
[4]  
Dimitrovska T, 2016, IEEE PES INNOV SMART
[5]   Fuzzy Control of Brushless Excitation System for Steam Turbogenerators [J].
Gunes, Mahit ;
Dogru, Necati .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2010, 25 (03) :844-852
[6]  
Hurley J.D., 2005, IEEE POW ENG SOC GEN
[7]  
Kundur Prabha, POWER SYSTEM ENG SER
[8]  
Lian S, 2010, INNOV SMART GRID TEC
[9]  
Liu Qiang, 2007, INT C EL MACH SYST I
[10]  
Lomei Hadi, 2016, IEEE T POWER SYSTEMS, P1