Performance analysis of a quasi-counter flow parallel-plate membrane contactor used for liquid desiccant air dehumidification

被引:55
作者
Huang, Si-Min [1 ]
Yang, Minlin [1 ]
Yang, Xiaoxi [1 ]
机构
[1] Dongguan Univ Technol, Dept Energy & Chem Engn, Key Lab Distributed Energy Syst Guangdong Prov, Dongguan 523808, Peoples R China
基金
中国国家自然科学基金;
关键词
Performance analysis; Parallel-plate; Liquid desiccant air dehumidification; Quasi-counter; Membrane contactor; MASS-TRANSFER; EXCHANGER; MODULE; MODEL;
D O I
10.1016/j.applthermaleng.2013.11.027
中图分类号
O414.1 [热力学];
学科分类号
摘要
A quasi-counter flow (combined counter/cross-flow) parallel-plate membrane contactor (QFPMC) is proposed and employed for liquid desiccant air dehumidification. The air and the liquid desiccant streams, in a quasi-counter flow arrangement, are separated by the selectively permeable membranes, which only allow the permeations of heat and water vapor while preventing other gases and liquid desiccant from permeating. A two-dimensional steady-state mathematical model is developed to study the performances in the QFPMC used for liquid desiccant air dehumidification. A finite difference method is employed to solve the equations governing momentum, heat and mass transports. The pressure drop, sensible cooling and dehumidification effectiveness are then obtained. An experimental work is conducted to validate the results. It can be found that compared to a cross-flow parallel-plate membrane contactor (CFPMC), the cooling and the dehumidification effectiveness of the QFPMC used for liquid desiccant air dehumidification are deteriorated by approximately 5-29% and 2-13%, respectively. Further, the solution channel pressure drop is increased by about 0.15-4.84 times. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:323 / 332
页数:10
相关论文
共 22 条
  • [1] Performance analysis of a membrane liquid desiccant air-conditioning system
    Abdel-Salam, Ahmed H.
    Ge, Gaoming
    Simonson, Carey J.
    [J]. ENERGY AND BUILDINGS, 2013, 62 : 559 - 569
  • [2] Cussler E.L., 2000, Diffusion: Mass Transfer in Fluid Systems, Vsecond
  • [3] Analytical model based performance evaluation, sizing and coupling flow optimization of liquid desiccant run-around membrane energy exchanger systems
    Ge, Gaoming
    Moghaddam, Davood Ghadiri
    Namvar, Ramin
    Simonson, Carey J.
    Besant, Robert W.
    [J]. ENERGY AND BUILDINGS, 2013, 62 : 248 - 257
  • [4] Conjugate heat and mass transfer in membrane parallel-plates ducts for liquid desiccant air dehumidification: Effects of the developing entrances
    Huang, Si-Min
    Zhang, Li-Zhi
    Yang, Minlin
    [J]. JOURNAL OF MEMBRANE SCIENCE, 2013, 437 : 82 - 89
  • [5] Turbulent Heat and Mass Transfer Across a Hollow Fiber Membrane Tube Bank in Liquid Desiccant Air Dehumidification
    Huang, Si-Min
    Zhang, Li-Zhi
    Tang, Kai
    Pei, Li-Xia
    [J]. JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2012, 134 (08):
  • [6] Fluid flow and heat mass transfer in membrane parallel-plates channels used for liquid desiccant air dehumidification
    Huang, Si-Min
    Zhang, Li-Zhi
    Tang, Kai
    Pei, Li-Xia
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2012, 55 (9-10) : 2571 - 2580
  • [7] Incropera FrankP., 2002, INTRO HEAT TRANSFER, V4th
  • [8] Heat transfer in pervaporation
    Karlsson, HOE
    Tragardh, G
    [J]. JOURNAL OF MEMBRANE SCIENCE, 1996, 119 (02) : 295 - 306
  • [9] Dehumidification and humidification of air by surface-soaked liquid membrane module with triethylene glycol
    Li, Jinlong
    Ito, Akira
    [J]. JOURNAL OF MEMBRANE SCIENCE, 2008, 325 (02) : 1007 - 1012
  • [10] Heat and mass transfer model of cross flow liquid desiccant air dehumidifier/regenerator
    Liu, X. H.
    Jiang, Y.
    Qu, K. Y.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (02) : 546 - 554