Investigation of a novel thermoelectric radiant air-conditioning system

被引:104
作者
Shen, Limei [1 ,2 ]
Xiao, Fu [2 ]
Chen, Huanxin [1 ]
Wang, Shengwei [2 ]
机构
[1] Huazhong Univ Sci & Technol, Dept Refrigerat & Cryogen, Wuhan 430074, Peoples R China
[2] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
关键词
Thermoelectric radiant air-conditioning (TE-RAC) system; Thermoelectric modules; Cooling and heating modes; Feasibility; Cooling and heating performances; THERMAL COMFORT; COOLING SYSTEMS; HEAT; TEMPERATURE; PERFORMANCE; COOLER; POWER;
D O I
10.1016/j.enbuild.2012.12.041
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper presents a novel thermoelectric radiant air-conditioning (TE-RAC) system, which employs the thermoelectric modules as radiant panels instead of conventional hydronic panels. The novel radiant system brings a lot of benefits including Freon free, convenient installation, no complex water distribution pipes, quiet and reliable operation, etc. Switching between cooling and heating modes can be easily achieved by reversing the input current. The purpose of this study is to investigate the feasibility and performance of the novel TE-RAC system, including its cooling and heating performances, condensation risk, dynamic thermal response and inertia, and cost-effectiveness. A case study of the TE-RAC system is presented to compare the TE-RAC system with conventional air-conditioning (AC) systems and radiant air-conditioning (RAC) systems in terms of cooling and heating capacities, energy consumption and operation reliability. It is found that the COP of the TE-RAC system could be comparable to conventional RAC systems and AC systems, besides many other benefits in life-cycle performances. (C) 2013 Elsevier B.V. All rights reserved.
引用
收藏
页码:123 / 132
页数:10
相关论文
共 48 条
[1]  
[Anonymous], 2011, 50019 CNS GB
[2]  
[Anonymous], 2012, 2011 BUILD EN DAT BO
[3]   Analyzing the dynamics of brain circuits with temperature: Design and implementation of a miniature thermoelectric device [J].
Aronov, Dmitriy ;
Fee, Michale S. .
JOURNAL OF NEUROSCIENCE METHODS, 2011, 197 (01) :32-47
[4]   Increase of COP in the thermoelectric refrigeration by the optimization of heat dissipation [J].
Astrain, D ;
Vián, JG ;
Domínguez, M .
APPLIED THERMAL ENGINEERING, 2003, 23 (17) :2183-2200
[5]   Effects of radiant temperature on thermal comfort [J].
Atmaca, Ibrahim ;
Kaynakli, Omer ;
Yigit, Abdulvahap .
BUILDING AND ENVIRONMENT, 2007, 42 (09) :3210-3220
[6]   Cooling, heating, generating power, and recovering waste heat with thermoelectric systems [J].
Bell, Lon E. .
SCIENCE, 2008, 321 (5895) :1457-1461
[7]   Thermoelectric cooling of a train carriage by using a coldness-recovery device [J].
Bojic, M ;
Savanovic, G ;
Trifunovic, N ;
Radovic, L ;
Saljic, D .
ENERGY, 1997, 22 (05) :493-500
[8]   Review of electronic transport models for thermoelectric materials [J].
Bulusu, A. ;
Walker, D. G. .
SUPERLATTICES AND MICROSTRUCTURES, 2008, 44 (01) :1-36
[9]   Experimental evaluation of heat transfer coefficients between radiant ceiling and room [J].
Causone, Francesco ;
Corgnati, Stefano P. ;
Filippi, Marco ;
Olesen, Bjarne W. .
ENERGY AND BUILDINGS, 2009, 41 (06) :622-628
[10]   Thermoelectric cooler application in electronic cooling [J].
Chein, R ;
Huang, GM .
APPLIED THERMAL ENGINEERING, 2004, 24 (14-15) :2207-2217