Rate of Legionella pneumophila colonization in hospital hot water network after time flow taps installation

被引:22
作者
Totaro, M. [1 ]
Valentini, P. [1 ]
Costa, A. L. [1 ]
Giorgi, S. [1 ]
Casini, B. [1 ]
Baggiani, A. [1 ]
机构
[1] Univ Pisa, Dept Translat Res & New Technol Med & Surg, Via S Zeno 35-39, I-56127 Pisa, Italy
关键词
Legionella; Time flow taps; Hospital water network; Chlorine dioxide;
D O I
10.1016/j.jhin.2017.08.021
中图分类号
R1 [预防医学、卫生学];
学科分类号
1004 ; 120402 ;
摘要
In hospital water systems legionellae may be resistant to disinfectants in pipework, which is a problem particularly in areas where there is low flow or stagnation of water. We evaluated legionella colonization of a water network of an Italian hospital after time flow taps (TFTs) installation in proximity to dead legs. The water volume flushed was 64 L/day from May 2016, and 192 L/day from December 2016. Before TFTs installation, Legionella pneumophila sg2-14 was detected in all points (4 x 10(4) +/- 3.1 x 10(4) cfu/L). All sites remained positive (2.9 x 10(4) +/- 1.9 x 10(4) cfu/L) through November 2016. From December 2016 legionella persisted in one point only (2 x 10(2) to 6.8 x 10(3) cfu/L). TFTs with chemical disinfection may reduce legionella colonization associated with dead legs. (C) 2017 The Healthcare Infection Society. Published by Elsevier Ltd. All rights reserved.
引用
收藏
页码:60 / 63
页数:4
相关论文
共 8 条
[1]   Water quality modeling in the dead end sections of drinking water distribution networks [J].
Abokifa, Ahmed A. ;
Yang, Y. Jeffrey ;
Lo, Cynthia S. ;
Biswas, Pratim .
WATER RESEARCH, 2016, 89 :107-117
[2]   Long-Term Effects of Hospital Water Network Disinfection on Legionella and Other Waterborne Bacteria in an Italian University Hospital [J].
Casini, Beatrice ;
Buzzigoli, Andrea ;
Cristina, Maria Luisa ;
Spagnolo, Anna Maria ;
Del Giudice, Pietro ;
Brusaferro, Silvio ;
Poscia, Andrea ;
Moscato, Umberto ;
Valentini, Paola ;
Baggiani, Angelo ;
Privitera, Gaetano .
INFECTION CONTROL AND HOSPITAL EPIDEMIOLOGY, 2014, 35 (03) :293-299
[3]  
European Centre for Disease Prevention and Control, 2015, LEG DIS EUR
[4]  
Grayman W.M., 2006, WATER DISTRIBUTION S, P1
[5]   Interactive Effects of Corrosion, Copper, and Chloramines on Legionella and Mycobacteria in Hot Water Plumbing [J].
Rhoads, William J. ;
Pruden, Amy ;
Edwards, Marc K. .
ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2017, 51 (12) :7065-7075
[6]  
Storey MV, 2004, SCAND J INFECT DIS, V36, P656, DOI 10.1080/00365540410020785
[7]  
Superior Institute of Health, 2015, LIN GUID PREV CONTR
[8]   Experimental comparison of point-of-use filters for drinking water ultrafiltration [J].
Totaro, M. ;
Valentini, P. ;
Casini, B. ;
Miccoli, M. ;
Costa, A. L. ;
Baggiani, A. .
JOURNAL OF HOSPITAL INFECTION, 2017, 96 (02) :172-176